2022-03-09 06:38:53 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22010260 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THERE ARE 2 ENERGY CALCULATIONS SUBMITTED FOR THIS |
| JOB. ONE IS DATED 12/06/2021 AND ONE IS DATED |
| 01/06/2022. THEY ARE TOTALLY DIFFERENT AS THE SQUARE |
| FOOTAGE AND MECHANICAL SYSTEM SIZING ARE DIFFERENT FOR |
| EACH DOCUMENT. PLEASE LET US KNOW WHICH DOCUMENT YOU |
| NEED FOR US TO LOCK OUT IN THE SYSTEM. FBC 107.2.1 |
| |
| 2) PLEASE SHOW THE RETURN AIR PATH FROM THE 1ST FLOOR |
| OFFICE BACK TO THE AHU WHEN THE POCKET DOORS ARE |
| CLOSED. FBC RES M1602.3 |
| |
| 3) PLEASE MAKE SURE THAT THE MECHANICAL EQUIPMENT SIZES |
| MATCH THE MECHANICAL EQUIPMENT SIZING CALCULATIONS THAT |
| IS CHOSEN FOR THIS PROJECT. FBC EC R403.7.1.2.1 |
| |
| 4) THE DESIGNER OF THE MECHANICAL DRAWING MUST PRINT |
| AND SIGN THEIR NAME IN THE TITLE BLOCK OF THE DOCUMENT. |
| WPB AMENDMENT 107.2.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |