2022-03-16 20:18:04 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SEVERAL RECEPTACLE WALL SPACING VIOLATIONS IN |
| OFFICE, FAMILY ROOM, LIVING ROOM, NEC 210.52 |
| |
| 2. SMOKE ALARMS OUTSIDE BEDROOMS MUST BE SMOKE/CARBON |
| COMBO ALARMS AND WITHIN 10' OF BEDROOM DOORS. FBC-RE |
| 314 AND 315, NFPA 72 |
| |
| 3. RISER DIAGRAM SHOWS 250AMP METER CAN. A 250AMP METER |
| CAN DOES NOT EXIST THERE IS A 200AMP METER CAN OR A |
| 320AMP CONTINUOUS METERCAN (400AMP) PLEASE SPECIFY |
| EXACT METER CAN TO BE USED. NEC 110.3B FBC 107.2.1 |
| |
| 4. ON RISER DIAGRAM PLAN SHOWS 250AMP MAIN SERVICE |
| DISCONNECTING MEANS AND PANEL A AS 250AMP M.L.O. PANEL |
| BUT ON 1ST FLOOR POWER PLAN DRAWING IT SHOWS 200AMP |
| MAIN SERVICE DISCONNECT SWITCH AND PANEL A AS 200AMPS. |
| PLEASE PROVIDE ACCURATE AND CONSISTENT DRAWINGS. FBC |
| 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-805-6744 |
| |
| |