Plan Review Notes
Plan Review Notes For Permit 22010238
Permit Number 22010238
Review Stop P
Sequence Number 2
Notes
Date Text
2022-11-21 12:05:062ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22010238
 11/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 BEACHSIDE POOL. THE REQUESTED RESPONSE NARRATIVE TO
 HELP EXPEDITE THE REVIEW WAS NOT PROVIDED. THE PLANS
 HAVE NOT BEEN COMPLETED CORRECTED. PLEASE CORRECT THE
 PLANS BASED ON THE COMMENTS AND PROVIDE A NARRATIVE
 RESPONSE
  
 1) 2ND REQUEST. PL0.20: REFER TO FAC 64 E-9.004 PRINTED
 BELOW AND VERIFY THE IRRIGATION SYSTEM WILL BE
 INSTALLED IN COMPLIANCE-
 64E-9.004: LANDSCAPE IRRIGATION WATER THAT WETS THE WET
 DECK AREA OF THE POOL, THE POOL ITSELF, ENTERS THE
 COLLECTOR TANK, OR WETS AN INTERACTIVE WATER FEATURE
 MUST BE POTABLE WATER FROM A PUBLIC WATER SYSTEM OR
 SHALL MEET THE BACTERIOLOGICAL QUALITY OF POTABLE WATER
 AS EVIDENCED BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO
 THE DEPARTMENT. RECLAIMED WATER MAY NOT BE USED IN
 THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY
 OF THE POOL (INSIDE OF THE POOL FENCE OR WITHIN 100
 FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP
 IRRIGATION OR SOAKER HOSES. SIGNS SHALL BE POSTED
 NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE
 AND IS NOT TO BE CONSUMED.
  
  
 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE
 REQUIRED HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE
 POOL DECK- SEC. 454.1.3.1.5 FBC B.
  
 3) PL6.00 & PL6.20: THE 4???6??? DEPTH AT THE POOL LIFT
 LOCATION EXCEEDS THE MAXIMUM 4??? ALLOWABLE- SEC.
 1009.2.1 FBC ACC.
  
 4) 2ND REQUEST FOR POOL LIFT SPECS. THE SPECS MAY BE A
 DEFERERED SUBMITTAL BY REQUEST. PL0.22 & PL6.00: PLEASE
 PROVIDE ENLARGED DIMENSIONED DETAILS ON THE PLANS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL LIFT
 INSTALLATION IN COMPLIANCE WITH THE FOLLOWING FBC ACC
 CODE SECTIONS:
 A) 1009.2.2 SEAT LOCATION.
 IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT
 SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM
 FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE
 CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A
 SLOPE NOT STEEPER THAN 1:48.
 B) 1009.2.3 CLEAR DECK SPACE.
 ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR
 DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT.
 THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL
 EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12
 INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK
 SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48.
 C) 1009.2.4 SEAT HEIGHT.
 THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW
 A STOP AT 16 INCHES (405 MM) MINIMUM TO 19 INCHES
 MAXIMUM MEASURED FROM THE DECK TO THE TOP OF THE SEAT
 SURFACE WHEN IN THE RAISED (LOAD) POSITION.
 D) 1009.2.6 FOOTRESTS AND ARMRESTS.
 FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE
 SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE
 WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE
 SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS
 E) 1009.2.7 OPERATION.
 THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM
 BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING
 MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN
 USE AND SHALL COMPLY WITH 309.4.
 F) 1009.2.8 SUBMERGED DEPTH.
 THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL
 SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW
 THE STATIONARY WATER LEVEL.
 G) 1009.2.9 LIFTING CAPACITY.
 SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY
 OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A
 STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
 LOAD.
  
  
 5) 2ND REQUEST. PL6.10: A) PROVIDE A SECTION VIEW OF
 THE POOL GUTTERS SHOWING COMPLIANCE WITH SECS.
 454.1.6.5.3.1 & 454.1.6.5.3.1.1 FBC. THE GUTTERS SHALL
 BE IDENTIFIED AS EITHER RECESSED OR OPEN TYPE. B) SHOW
 THE DRAIN SPACINGS ON THE PLAN OR PROVIDE A NOTE TO
 INDICATE SPACING NOT TO EXCEED 10FT. C) CONCERNING
 PERIMETER OVERFLOW GUTTERS: THE LIP OF THE GUTTER SHALL
 BE UNIFORMLY LEVEL WITH A MAXIMUM TOLERANCE OF 1/4 INCH
 BETWEEN THE HIGH AND LOW AREAS. THE BOTTOM OF THE
 GUTTER SHALL BE LEVEL OR SLOPE TO THE DRAINS. E) IT
 APPEARS THE GUTTERS DO NOT EXTEND ALONG THE ENTIRE
 PERIMETER OF THE POOL. THE EXCEPTION ALLOWS GUTTER
 ELIMINATION AT A LENGTH NOT TO EXCEED 15 FT. AND NOT TO
 EXCEED 10 PERCENT OF THE PERIMETER.
  
 13) 2ND REQUEST PL6.10: SHOW THE SPACING MEASUREMENTS
 BETWEEN THE WALL INLETS IN COMPLIANCE WITH SEC.
 454.1.6.5.9.1 FBC B. A) PROVIDE A POOL INLET DETAIL-
 SEC. 454.1.6.5.9 FBC P.
  
 14) 2ND REQUEST PL6.11, PL6.15: CLARIFY IF A GUTTER
 DRAIN OR INFINITY DRAIN WILL BE INSTALLED. IT APPEARS
 THAT THE INFINITY DESIGNATION ON PL6.15 IS AN ERROR.
 PLEASE CLARIFY- SEC. 107.2.1 WPB
  
 15) 2ND REQUEST PL6.11: CLARIFY IF PREVAILING WIND
 DIRECTION WAS CONSIDERED BY THE DESIGNER OF RECORD IN
 THE SELECTION OF THE SKIMMER LOCATIONS- SEC.
 454.1.6.5.3.2.2 FBC B.
  
 17) 2ND REQUEST. PL6.30: SHOW THE LOCATION OF THE
 REQUIRED HOSE BIB WITH VACUUM BEAKER IN THE EQUIPMENT
 ROOM- SEC. 454.1.5.9 FBC B.
  
 19) 2ND REQUEST PL6.30: PROVIDE AN ENLARGED
 INSTALLATION AND PIPING DETAIL FOR THE WASTEWATER SUMP
 PUMP AND PIT. PLEASE INCLUDE AN EQUIPMENT SCHEDULE FOR
 THE PUMP- SECS. 1113.1- 1113.1.2 FBC P. PLEASE NOTE THE
 WASTEWATER SHALL BE DECHLORINATED AND DRAIN INTO THE
 STORM SYSTEM- SEC. 90-205 (1) WPB.
  
 20) 2ND REQUEST. PL6.30: SHOW THE EQUIPMENT ROOM DOOR
 IS EQUIPPED WITH A LOCKABLE DOOR OR OTHERWISE PROTECTED
 FROM UNAUTHORIZED ACCESS- 454.1.5.9 FBC B.
  
 21) 2ND REQUEST. PL6.00 & PL6.30: PROVIDE A CLEANING
 SYSTEM FOR THE POOL IN ACCORDANCE WITH SEC.
 454.1.6.5.12 FBC B. PLEASE NOTE A PORTABLE, ROBOTIC OR
 PLUMBED-IN VACUUM CLEANING SYSTEM SHALL BE PROVIDED.
  
 23) 2ND REQUEST. PL6.30: PLEASE SHOW COMPLIANCE WITH
 THE FOLLOWING CODE SECTIONS FROM THE FBC EC:
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 24) SUMMARY OF SEPARATELY PERMITTED ITEMS.
 A) SANITARY FACILITIES.
 B) POOL SHOWER AND HOSE BIBS.
 C) GAS WATER HEATER AND GAS PIPING.
 D) EQUIPMENT ENCLOSURE BUILDING INCLUDING THE
 MECHANICAL AND ELECTRICAL WORK.
 E) PLUMBING FIXTURES IN THE EQUIPMENT ENCLOSURE
 INCLUDING THE HOSE BIB AND SUMP PUMP
 F) POOL FENCE AND GATES.
 G) POOL DECK.
 H) CIVIL ENGINEERING.
  
 25) SUMMARY OF SUBMITTALS OR DEFERRED SUBMITTALS:
 A) POOL LIFT.
 B) MAIN DRAIN ASSEMBLIES AND COVERS.
 C) POOL PUMP.
 D) COLLECTOR TANK.
 E) FILTERS.
 F) SKIMMERS
 G) CHLORINATION EQUIPMENT
  
 NEW COMMENTS.
  
 1) SHEET PL0.20: PLEASE ADD THESE REQUIRED ITEMS ON THE
 PLAN FOR THE POOL BATHROOMS.
 A) DIAPER CHANGING STATIONS- SEC. 454.1.6.1.1 FBC B.
 B) HOSE BIBS IN OR WITHIN 25 FT. OF THE BATHROOMS- SEC.
 454.1.6.1.4
 C) FLOOR DRAINS IN THE BATHROOMS- SEC. 454.1.6.1.3.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER