2022-12-01 15:58:38 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22010237 |
| 12/1/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COURTYARD POOL REVIEW COMMENTS. |
| |
| 1) SHEET PL0.20 COURTYARD POOL, NORTH & SOUTH SPA |
| BATHROOMS. |
| |
| A) REFER TO SEC. 403.6.1 FBC P: POOL BATHROOMS FOR |
| FEMALE USE SHALL HAVE A RATIO OF THREE TO TWO WATER |
| CLOSETS PROVIDED AS THE COMBINED TOTAL OF WATER CLOSETS |
| AND URINALS PROVIDED FOR MALE USE. |
| |
| B) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| SHALL CONTAIN A DIAPER CHANGING STATION- SEC. |
| 454.1.6.1.1. |
| |
| C) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| SHALL CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3. |
| |
| D) SHOW THE LOCATIONS OF REQUIRED HOSE BIBS WITHIN 25 |
| FT. OF EACH BATHROOM AND NOTE THAT EACH WILL BE |
| EQUIPPED WITH A VACUUM BREAKER- SEC. 454.1.6.1.4. |
| |
| E) CONFIRM WITH DETAILS AND/OR NOTES THAT THE FLOOR |
| INSIDE THE HALLWAY LEADING TO THE POOL BATHROOMS AND |
| THE POOL BATHROOM FLOORS ARE CONSTRUCTED OF CONCRETE OR |
| OTHER NON-ABSORBENT MATERIALS AND HAVE A SMOOTH, SLIP |
| RESISTANT FINISH. INDICATE THE FLOORS SLOPE TO THE |
| FLOOR DRAINS IN THE BATHROOMS. |
| |
| 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE |
| REQUIRE HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE |
| POOL DECK- SEC. 454.1.3.1.5 FBC B. |
| |
| 3) 2ND REQUEST. PL0.24 &PL0.26: SHOW THE POTABLE WATER |
| RUNS FROM THE WATER SOURCE TO THE COLLECTOR TANKS AND |
| LOCATIONS OF POTABLE WATER BACKFLOW PREVENTERS- SEC. |
| 107.2.1 WPB AND SEC. 454.1.6.3 FBC B |
| |
| 4) 2ND REQUEST. PL0.24 &PL0.26: SHOW THE GAS PIPING |
| RUNS FROM THE GAS SOURCE TO THE POOL HEATERS AND ALL |
| OTHER GAS FIRED EQUIPMENT OR APPLIANCES. PLEASE PLACE A |
| NOTE TO INDICATE THE GAS POOL HEATERS AND GAS PIPING |
| SHALL BE INSTALLED UNDER A SEPARATE PERMIT. |
| |
| 5) PL3.21: THE REQUIRED HYDROSTATIC RELIEF VALVE (ITEM |
| #7) IS NOT SHOWN IN THE DETAIL- SEC. 454.1.6.5.10.4 FBC |
| B. |
| |
| 6) 2ND REQUEST- PL3.11: SHOW GUTTER DRAIN SPACING |
| DIMENSIONS- SEC. 454.1.6.5.3.1 FBC B. PLEASE NOTE THE |
| DEPTH MARKING OF 3'0" AT THE SUNSHELF ON PL3.11 & |
| PL3.10 NEEDS TO BE CHANGED TO SHOW 8". |
| |
| 7) DEFERRED SUBMITTALS: ALL POOL AND SPA RECIRCULATION |
| EQUIPMENT SHALL BE DEFERRED SUBMITTALS WHICH SHALL BE |
| ONSITE AT TIME OF INSPECTION- SEC. 107.3.4.1 WPB.. EACH |
| SUBMITTAL SHALL BEAR THE APPROVAL STAMP OF THE ENGINEER |
| OF RECORD. THE SUBMITTALS SHALL INCLUDE BUT NOT BE |
| LIMITED TO: |
| |
| A) PUMPS. |
| |
| B) MAIN DRAIN ASSEMBLIES INCLUDING FRAMES, COVERS, AND |
| SUMPS. |
| |
| C) COLLECTOR TANKS |
| |
| D) FILTERS |
| |
| E) SKIMMERS |
| |
| F) EQUALIZER FITTINGS |
| |
| G) HYDROSTATIC RELIEF VALVES |
| |
| H) CHLORINATION AND DECHLORINATION EQUIPMENT |
| |
| I) ADA LIFTS |
| |
| J) EMERGENCY SHOWER AND EYE WASH STATIONS |
| |
| |
| NORTH AND SOUTH SPA REVIEW COMMENTS. |
| |
| 1) SHEET PL0.20 COURTYARD POOL, NORTH & SOUTH SPA |
| BATHROOMS: IN RESPONSE TO 1ST REVIEW COMMENT #1, AN |
| UPDATED SHEET PL0.20 HAS BEEN PROVIDED WHICH SHOWS THE |
| LOCATIONS OF THE POOL AND SPA BATHROOMS IN AN ADJACENT |
| BUILDING WITH A TRAVEL DISTANCE EXCEEDING THE ALLOWABLE |
| 50 FT. PER SEC. 454.1.6.1.2 FBC B. THE LOCATIONS ARE |
| LIMITED TO 50 FT. BECAUSE THE RESTROOM DOORS DO NOT |
| OPEN DIRECTLY TO THE OUTSIDE. DIRECTIONAL SIGNS WOULD |
| ALSO BE REQUIRED TO BE POSTED WITH DIRECTIONS LEGIBLE |
| FROM ANY PORTION OF THE POOL DECK. |
| |
| A) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| SHALL CONTAIN A DIAPER CHANGING STATION- SEC. |
| 454.1.6.1.1. |
| |
| B) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| SHALL CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3. |
| |
| C) SHOW THE LOCATIONS OF REQUIRED HOSE BIBS WITHIN 25 |
| FT. OF EACH BATHROOM AND NOTE THAT EACH WILL BE |
| EQUIPPED WITH A VACUUM BREAKER- SEC. 454.1.6.1.4. |
| |
| D) CONFIRM WITH DETAILS AND/OR NOTES THAT THE FLOOR |
| INSIDE THE HALLWAY LEADING TO THE POOL BATHROOMS AND |
| THE POOL BATHROOM FLOORS ARE CONSTRUCTED OF CONCRETE OR |
| OTHER NON-ABSORBENT MATERIALS AND HAVE A SMOOTH, SLIP |
| RESISTANT FINISH. INDICATE THE FLOORS SLOPE TO THE |
| FLOOR DRAINS IN THE BATHROOMS |
| |
| 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE |
| REQUIRE HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE |
| POOL AND SPA DECK- SEC. 454.1.3.1.5 FBC B. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |