2022-02-03 16:49:33 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22010237 |
| 2/3/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COURTYARD POOL REVIEW COMMENTS. |
| |
| 1) SHEETS PL0.20 & PL3.00: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS FOR THE POOL AND SHOW THE LOCATIONS OF THE |
| SANITARY FACILITIES- TABLE 454.1.6.1 AND SECS. |
| 454.1.6.1- 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION |
| UNDER SEC. 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS |
| ON THE PLAN TO VERIFY COMPLIANCE. THE SUBMITTED PLANS |
| DO NOT CLEARLY INDICATE THE LOCATIONS OF THE POOL |
| BATHROOMS AND WHICH BATHROOMS ARE DESIGNATED FOR USERS |
| OF THE POOL, SPAS, AND DECK AREAS. PROVIDE COMPLIANCE |
| DETAILS AND INFORMATION AS REQUIRED BY SECS. |
| 454.1.6.1.1- 454.1.6.1.4 FBC B. PLEASE NOTE THE |
| REQUIRED SANITARY FACILITIES AND PLUMBING FIXTURES |
| REQUIRED FOR THE POOL AREA (BATHROOM FIXTURES, HOSE |
| BIBS, POOL SHOWERS ) AND IN THE EQUIPMENT ROOM- (SUMP |
| PUMP AND EMERGENCY SHOWER AND EYEWASH ETC.) SHALL BE |
| INSTALLED UNDER SEPARATE PERMITS- SECS. 105.1 & 107.2.1 |
| WPB. |
| |
| 2) PL0.20: REFER TO FAC 64 E-9.004 PRINTED BELOW AND |
| VERIFY THE IRRIGATION SYSTEM WILL BE INSTALLED IN |
| COMPLIANCE- |
| 64E-9.004: LANDSCAPE IRRIGATION WATER THAT WETS THE WET |
| DECK AREA OF THE POOL, THE POOL ITSELF, ENTERS THE |
| COLLECTOR TANK, OR WETS AN INTERACTIVE WATER FEATURE |
| MUST BE POTABLE WATER FROM A PUBLIC WATER SYSTEM OR |
| SHALL MEET THE BACTERIOLOGICAL QUALITY OF POTABLE WATER |
| AS EVIDENCED BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO |
| THE DEPARTMENT. RECLAIMED WATER MAY NOT BE USED IN |
| THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY |
| OF THE POOL (INSIDE OF THE POOL FENCE OR WITHIN 100 |
| FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP |
| IRRIGATION OR SOAKER HOSES. SIGNS SHALL BE POSTED |
| NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE |
| AND IS NOT TO BE CONSUMED. |
| |
| 3) PL0.20, PL0.24 & PL0.26: SHOW THE WASTEWATER |
| RECEPTORS AND THE PIPING RUNS TO PLACES OF DISPOSAL, OR |
| CONNECTION POINTS AT STORM MAINS. PLEASE NOTE THE |
| FOLLOWING CONCERNING POOL WASTEWATER: |
| WASTEWATER FROM THE POOL AND THE POOL EQUIPMENT SHALL |
| BE DECHLORINATED AND DISCHARGED THROUGH AN AIR GAP IN |
| THE INTO THE STORM DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & |
| SEC. 90-126(5) WPB CODE OF ORDINANCES. THE WASTEWATER |
| SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM. PLEASE |
| REVIEW WPB BUILDING DEPT. GUIDELINES FOR POOL WATER |
| DISPOSAL. THE ENGINEER OF RECORD SHALL SHOW THE |
| DECHLORINATION SYSTEM ON THE PLAN AND PROVIDE |
| SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE SEE GUIDELINES |
| BELOW- |
| |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 4) PL0.24 &PL0.26: SHOW THE POTABLE WATER RUNS FROM THE |
| WATER SOURCE TO THE COLLECTOR TANKS AND LOCATIONS OF |
| POTABLE WATER BACKFLOW PREVENTERS- SEC. 107.2.1 WPB AND |
| SEC. 454.1.6.3 FBC B. PLEASE NOTE THAT SEPARATE PERMITS |
| ARE REQUIRED FOR THE BACKFLOW PREVENTERS- SEC. 105.1 |
| WPB. FL. LICENSED PLUMBING CONTRACTORS SHALL OBTAIN |
| SEPARATE PERMITS FOR INSTALLATION OF THE BACKFLOW |
| PREVENTERS IN ACCORDANCE WITH SECTION 105.1WPB AND SEC. |
| 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| 5) PL0.20: PLEASE PROVIDE AN ENLARGED POOL DECK DRAWING |
| SHOWING COMPLIANCE WITH SECS. 454.1.3.1.2- 454.1.3.1.5 |
| FBC B- DECK SLOPES, UNOBSTRUCTED WIDTHS, SLIP-RESISTANT |
| SURFACES FOR THE DECK AND WALKWAYS. |
| |
| 6) PL0.20: SHOW THE LOCATION OF THE REQUIRE HOSE BIB OR |
| BIBS WITH VACUUM BREAKERS FOR THE POOL DECK- SEC. |
| 454.1.3.1.5 FBC B. |
| |
| 7) PL0.24 &PL0.26: SHOW THE GAS PIPING RUNS FROM THE |
| GAS SOURCE TO THE POOL HEATERS AND ALL OTHER GAS FIRED |
| EQUIPMENT OR APPLIANCES. PLEASE PLACE A NOTE TO |
| INDICATE THE GAS POOL HEATERS AND GAS PIPING SHALL BE |
| INSTALLED UNDER A SEPARATE PERMIT. |
| |
| 8) PL0.20 & PL0.24: PLEASE SHOW THE GRAVITY PIPING RUNS |
| FROM THE POOL DRAINS TO THE COLLECTOR TANK AND THE |
| SUCTION DRAIN LINES FROM THE TANK TO THE PUMP- SEC. |
| 454.1.6.5.3 & 454.1.6.5.10.5 FBC B. PROVIDE A |
| CROSS-SECTION VIEW OF THE PIPE RUNS SHOWING THE SLOPES. |
| |
| 9) PL3.00 & PL3.05: SHOW THE POOL DEPTH AT THE POOL |
| LIFT LOCATION- SEC. 1009.2.1 WPB, AND AT ALL LEVELS OF |
| THE POOL- SEC. 454.1.2.2.4 FBC B. |
| |
| 10) PL0.22 & PL3.00: PLEASE PROVIDE ENLARGED |
| DIMENSIONED DETAILS ON THE PLANS AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR THE POOL LIFT |
| INSTALLATION IN COMPLIANCE WITH THE FOLLOWING FBC ACC |
| CODE SECTIONS: |
| A) 1009.2.2 SEAT LOCATION. |
| IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT |
| SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM |
| FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE |
| CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A |
| SLOPE NOT STEEPER THAN 1:48. |
| B) 1009.2.3 CLEAR DECK SPACE. |
| ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR |
| DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT. |
| THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL |
| EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12 |
| INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK |
| SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48. |
| C) 1009.2.4 SEAT HEIGHT. |
| THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW |
| A STOP AT 16 INCHES (405 MM) MINIMUM TO 19 INCHES |
| MAXIMUM MEASURED FROM THE DECK TO THE TOP OF THE SEAT |
| SURFACE WHEN IN THE RAISED (LOAD) POSITION. |
| D) 1009.2.6 FOOTRESTS AND ARMRESTS. |
| FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE |
| SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE |
| WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE |
| SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS |
| E) 1009.2.7 OPERATION. |
| THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM |
| BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING |
| MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN |
| USE AND SHALL COMPLY WITH 309.4. |
| F) 1009.2.8 SUBMERGED DEPTH. |
| THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL |
| SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW |
| THE STATIONARY WATER LEVEL. |
| G) 1009.2.9 LIFTING CAPACITY. |
| SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY |
| OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A |
| STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED |
| LOAD. |
| |
| 11) PL3.00 DATA BLOCK: REFER TO SEC. 454.1.1.1 FBC B. |
| AND CLARIFY IF THE POOLS FOR THE FACILITY HAVE BEEN |
| SIZED TO ACCOMODATE A TRANIENT OR NON-TRANSIENT BATHING |
| LOAD. PROVIDE NOTES AND CALCULATIONS BASED ON THE TOTAL |
| LIVING UNITS OF THE FACILTIY. |
| |
| 12) PL3.00, PL3.05, PL3.10: SHOW THE MAIN DRAINS ARE |
| LOCATED AT THE DEEPEST POINT OF THE POOL- SEC. |
| 454.1.6.5.10 FBC B. PLEASE NOTE IF THE WIDTH OF THE |
| DEEPEST PORTION OF THE POOL IS GREATER THAN 30 FT THE |
| DRAINS SHALL BE EQUALLY SPACED FROM THE POOL SIDE WALLS |
| AND EACH OTHER- SEC. 454.1.6.5.10.3 |
| |
| 13) PL3.00 & PL3.2.1: SUBMIT SPECS FOR THE MAIN DRAIN |
| ASSEMBLIES AND DRAIN COVERS- SEC. 454.1.6.5.10.2 FBC B. |
| |
| 14) PL3.01: PLEASE CORRECT THE DEPTH MARKINGS TO BE |
| CONSISTENT WITH THE DEPTHS OF THE POOL AND THE SUN |
| SHELF- SECS. 454.1.2.3 & 454.1.2.8 FBC B. A) SHOW THE |
| ACTUAL DEPTH OF THE SUN SHELF MEASURED FROM THE COPING |
| AND THE SHELF FLOOR, AND CLARIFY OF AN OPEN-TYPE GUTTER |
| SYSTEM WILL BE INSTALLED AND USED AS A STEP- SEC. |
| 454.1.2.3.8 FBC B. |
| |
| 15) PL3.11: A) PROVIDE A SECTION VIEW OF THE POOL |
| GUTTERS AND SUN SHELF GUTTERS SHOWING COMPLIANCE WITH |
| SECS. 454.1.6.5.3.1 & 454.1.6.5.3.1.1 FBC. THE GUTTERS |
| SHALL BE IDENTIFIED AS EITHER RECESSED OR OPEN TYPE. B) |
| SHOW THE DRAIN SPACINGS ON THE PLAN OR PROVIDE A NOTE |
| TO INDICATE SPACING NOT TO EXCEED 10FT. C) CONCERNING |
| PERIMETER OVERFLOW GUTTERS: THE LIP OF THE GUTTER SHALL |
| BE UNIFORMLY LEVEL WITH A MAXIMUM TOLERANCE OF 1/4 INCH |
| BETWEEN THE HIGH AND LOW AREAS. THE BOTTOM OF THE |
| GUTTER SHALL BE LEVEL OR SLOPE TO THE DRAINS. |
| |
| 16) PL3.11: SHOW THE SPACING MEASUREMENTS BETWEEN THE |
| FLOOR INLETS AND FROM ADJACENT WALLS IN COMPLIANCE WITH |
| SEC. 454.1.6.5.9.4. A) PROVIDE A POOL INLET DETAIL- |
| SEC. 454.1.6.5.9.5 FBC P. |
| |
| 17) PL3.11 & PL3.32: PLEASE MATCH THE COLLECTOR TANK |
| DETAIL DRAIN AND SUCTION PIPE SIZES SHOWN ON THE DETAIL |
| WITH THE SIZES SHOWN ON THE PLAN- SEC. 107.2.1 WPB. A) |
| SHOW THE LOCATION OF THE TANK IS IN A LOCKABLE |
| ENCLOSURE OR OTHERWISE PROTECTED FROM UNAUTHORIZED |
| ACCESS (LOCKABLE LID?)- SEC. 454.1.5.1 FBC B. SHOW |
| MEANS OF ACCESS FOR CLEANING, SERVICE AND INSPECTION- |
| 454.1.5.5. PLEASE SUBMIT A SPEC SHEET FOR THE TANK. |
| |
| 18) PL3.00, PL3.15, PL3.30: SUBMIT MANUFACTURER'S SPECS |
| FOR THE PUMP AND PROVIDE THE PUMP CURVE IN COMPLIANCE |
| WITH SEC. 454.1.6.5.4 FBC B. |
| |
| 19) PL3.30: SHOW THE LOCATION OF THE REQUIRED HOSE BIB |
| WITH VACUUM BEAKER IN THE EQUIPMENT ROOM- SEC. |
| 454.1.5.9 FBC B. |
| |
| 20) PL3.30: THE SAND FILTERS ARE IDENTIFIED AS ITEM #2 |
| IN THE SCHEDULE BUT ARE LABELED AS COLLECTOR TANK ITEM |
| #3) IN THE LAYOUT PLAN. PLEASE NOTE SHEET PL0.20 SHOWS |
| THE TANK CLOSE TO THE POOL DECK AND NOT IN THE |
| ENCLOSURE- SEC. 107.2.1 WPB. |
| |
| 21) PL3.30: SHOW THE LOCATION OF THE EMERGENCY SHOWER |
| AND EYEWASH (ITEM #11) IN THE LAYOUT PLAN- SEC. 107.2.1 |
| WPB. |
| |
| 22) PL3.30: PLEASE SHOW THE LOCATIONS OF ITEMS- 4, 5, |
| 6, 7, 8 IN THE LAYOUT PLAN- 107.2.1 WPB. |
| |
| 23) PL3.30: PROVIDE AN ENLARGED INSTALLATION AND PIPING |
| DETAIL FOR THE WASTEWATER SUMP PUMP AND PIT. PLEASE |
| INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP- SECS. |
| 1113.1- 1113.1.2 FBC P. REFER TO COMMENT #3 CONCERNING |
| WASTEWATER DISPOSAL AND SHOW COMPLIANCE. |
| |
| 24) PL3.30: SHOW THE EQUIPMENT ROOM DOOR IS EQUIPPED |
| WITH A LOCKABLE DOOR OR OTHERWISE PROTECTED FROM |
| UNAUTHORIZED ACCESS- 454.1.5.9 FBC B. |
| |
| 25) PL3.00 & PL3.30: PROVIDE A CLEANING SYSTEM FOR THE |
| POOL IN ACCORDANCE WITH SEC. 454.1.6.5.12 FBC B. PLEASE |
| NOTE A PORTABLE, ROBOTIC OR PLUMBED-IN VACUUM CLEANING |
| SYSTEM SHALL BE PROVIDED. |
| |
| 26) PL3.30: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE |
| FILTERS, CHLORINATOR, FEEDERS, AND SPA SKIMMERS SHOWING |
| THE EQUIPMENT CONFORMS WITH REQUIRED STANDARDS NSF/ANSI |
| STANDARD 50, CIRCULATION SYSTEM COMPONENTS AND RELATED |
| MATERIALS FOR SWIMMING POOL, SPAS/HOT TUBS, DATED APRIL |
| 2007- SECTION 454.1.6.5.1 FBC B. |
| |
| 27) PL3.30: PLEASE SHOW COMPLIANCE WITH THE FOLLOWING |
| CODE SECTIONS FROM THE FBC EC: |
| C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS |
| SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF |
| SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED |
| ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND |
| WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH |
| SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER |
| THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A |
| CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED |
| HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING |
| IGNITION PILOTS. |
| C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL |
| METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS |
| AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE |
| INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP |
| MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN |
| COMPLIANCE WITH THIS SECTION. |
| EXCEPTIONS: |
| 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP |
| OPERATION. |
| 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY |
| POOL HEATING SYSTEMS. |
| C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND |
| OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A |
| VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS. |
| |
| 28) SUMMARY OF SEPARATE PERMITS REQUIRED: |
| |
| A) POTABLE WATER BACKFLOW PREVENTERS. |
| B) SANITARY FACILITIES. |
| C) POOL SHOWER AND HOSE BIBS. |
| D) GAS WATER HEATER AND GAS PIPING. |
| E) EQUIPMENT ENCLOSURE BUILDING INCLUDING THE |
| MECHANICAL AND ELECTRICAL WORK. |
| F) PLUMBING FIXTURES IN THE EQUIPMENT ENCLOSURE |
| INCLUDING THE HOSE BIB, EMERGENCY SHOWER, FLOOR DRAIN, |
| AND SUMP PUMP |
| G) POOL FENCE AND GATES. |
| H) POOL DECK. |
| I) CIVIL ENGINEERING. |
| |
| 29) SUMMARY OF SUBMITTALS OR DEFERRED SUBMITTALS: |
| |
| A) POOL LIFT. |
| B) MAIN DRAIN ASSEMBLIES AND COVERS. |
| C) POOL PUMP. |
| D) COLLECTOR TANK. |
| E) FILTERS. |
| F) SKIMMERS |
| G) CHLORINATION EQUIPMENT |
| |
| NORTH AND SOUTH SPA REVIEW COMMENTS. |
| |
| 1) COMMENTS 1-10, 12, 13, 18, 19, 23, 24, 25, 26, 27, & |
| 28 FROM THE COURTYARD POOL REVIEW ABOVE ARE ALSO |
| APPLICABLE TO THE SPA REVIEWS. |
| |
| 2) PL0.20: SHOW THE LOCATIONS OF THE SPA POOL SIGNS AND |
| CLOCKS- SECS. 454.1.18.13 & 454.1.18.14 FBC B. |
| |
| 3) PL0.20: CLARIFY IF THE SPAS WILL BE EQUIPPED WITH |
| EMERGENCY CUT OFF SWITCHES. REFER TO SEC. 454.1.18.15 |
| FBC B AND PROVIDE DETAILS IF APPLICABLE. |
| |
| 4) PL4.00 & PL5.00: SHOW DEPTH MARKING LOCATIONS- SEC. |
| 454.1.2.3.1 FBC B. |
| |
| 5) PL4.11, PL4.15, PL5.10 & PL5.15: IDENTIFY THE |
| LOCATIONS OF PROPORTIONAL VALVES ON ALL RECIRCULATION |
| LINES- SEC. 454.1.8.8 FBC B. |
| |
| 6) PL4.00: REFER TO SECS. 454.1.1.1 & 454.1.7.9 FBC B |
| AND SHOW COMPLIANCE- AUTOMATED OXIDATION REDUCTION |
| POTENTIAL (ORP) AND PH CONTROLLERS WITH SENSING PROBES |
| SHALL BE PROVIDED TO ASSIST IN MAINTAINING PROPER |
| DISINFECTION AND PH LEVELS. |
| |
| 7) PL4.15 & PL5.15: THE DRAWINGS SHOW A FEATURE PUMP |
| THAT IS SUPPLYING WATER FROM THE COLLECTOR TANKS TO |
| WATER SPOUTS. PLEASE SHOW THE LOCATIONS OF THE WATER |
| FEATURE AND SPOUTS ON THE PLANS AND PROVIDE DETAILS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |