Plan Review Notes
Plan Review Notes For Permit 22010237
Permit Number 22010237
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-31 08:42:56PLAN
 REVIEW COMMENTS FOR COURTYARD POOL AND NORTH & SOUTH
 SPAS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THAT THE SANITARY FACILITIES FOR THE POOL MEET
 THE REQUIREMENTS OF FBC 454.1.6.1.
  
 2) REVISE THE POOL RULES SIGN ON SHEET 011-PL0.22 TO
 REFLECT THE 2020 FBC 454.1.2.3.5 REQUIREMENTS FOR
 MAXIMUM POOL DEPTH AND ALLOWING COMMERCIALLY BOTTLED
 WATER ON THE WET DECK.
  
 3) THE POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 SHOW HOW THE POOL AND POOL EQUIPMENT WILL COMPLY WITH
 FBC 1612.4.2.
  
 4) THE LOCATION MAP AND SITE ADDRESS ON THE COVER SHEET
 IS NOT FOR THIS PROJECT. PLEASE CORRECT. FBC 107.2.1
  
 5) THIS IS AN AREA OF QUESTIONABLE SOILS. SUBMIT A
 GEOTECHNICAL REPORT FOR THE POOL. FBC 1603.1 AND
 1603.1.6
  
 6) SHOW HOW THE POOL EQUIPMENT IS ANCHORED TO RESIST
 WIND LOADS. FBC 1601.1 AND 1603.1.4
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE COURTYARD POOL
 AND THE TWO SPA POOLS. FBC AMENDMENTS 107.2.1
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 9) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  