Plan Review Notes
Plan Review Notes For Permit 22010192
Permit Number 22010192
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-20 17:21:50NEW SINGLE FAMILY RESIDENCE (R3) BUILDING AUDIT
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010192
  
 1- LOT DRAINAGE
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- PROPOSED SITE PLAN PLAN SHOWS RETAINING WALLS. THESE
 WALLS ARE NOT PART OF THIS BUILDING PERMIT. SEPARATE
 PERMIT IS REQUIRED FOR THESE WALLS. SEC. 105.1 CITY
 AMENDMENTS.
  
 3- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 FBC-RESIDENTIAL.
  
 4- NEED BATHROOM ON THE FIRST FLOOR WITH MAXIMUM
 POSSIBLE PRIVACY AND A DOOR THAT PROVIDES 29" MIN.
 CLEAR OPENING AS REQUIRED BY SEC. R320.1.1
 FBC-RESIDENTIAL.
  
 5- PLANS DON'T PROVIDE DETAILS AND SPECIFICATIONS FOR
 THE CONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE
 WITH THE REQUIREMENTS OF SEC. R311.7 FBC-RESIDENTIAL
 AND TABLE R301.5 FBC-RESIDENTIAL.
  
 6- PLANS DON'T PROVIDE DETAILS AND SPECIFICATIONS FOR
 THE CONSTRUCTION OF BALCONY GUARDRAILS SHOWING
 COMPLIANCE WITH THE REQUIREMENTS OF SEC. R312.1
 FBC-RESIDENTIAL AND TABLE R301.5 FBC-RESIDENTIAL
  
 7- PLANS DON'T PROVIDE DETAILS AND SPECIFICATIONS FOR
 THE CONSTRUCTION OF THE TERRACOTA BARREL TILE BALCONY
 GUARDRAILS SHOWING COMPLIANCE WITH THE REQUIREMENTS OF
 SEC. R312.1 FBC-RESIDENTIAL AND TABLE R301.5
 FBC-RESIDENTIAL.
  
 8- NEED TO SPECIFY ATTIC ACCESS SIZE AND LOCATION IN
 MASTER BEDROOM WING SHOWING COMPLIANCE WITH SEC. R807
 FBC-RESIDENTIAL.
  
 9-SHEET S-500:
 A)ENGINEER NEEDS TO UPDATE THE PRESSURE ZONES ON THE
 UPLIFT LOADS COMPONENTS & CLADDING DIAGRAM TO REFLECT
 THE CURRENT ZONES AS SHOWN ON FIGURE
 R301.2(7)FBC-RESIDENTIAL.
  
 B)ENGINEER NEEDS TO REVISE DIMENSION "A". FOOTNOTE "A"
 ON FIGURE R301.2(7)FBC-RESIDENTIAL REQUIRES THIS
 DISTANCE TO BE 4'-0" MIN.
  
 C)USING TABLE R301.2(2)FBC-RESIDENTIAL AS A REFERENCE,
 IT LOOKS LIKE THE UPWARD DESIGN PRESSURES SPECIFIED FOR
 ROOF ZONES 1 AND 2 ARE LOW. REVISE AS REQUIRED OR
 PROVIDE CALCULATIONS SHOWING WHY THEY ARE SO LOW
 COMPARED TO THE REVISED 2020 FBC-RESIDENTIAL TABLE.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 10- WINDOWS AND DOORS DESIGN PRESSURES SPECIFIED ON
 DRAWINGS S100 AND S200 ARE LOW FOR OPENINGS LOCATED ON
 THE END ZONE (NOTE: SEE ITEM #9(B) FOR MINIMUM END ZONE
 DIMENSION). REVISE AS REQUIRED OR PROVIDE CALCULATIONS
 SHOWING WHY THEY ARE SO LOW COMPARED TO THE REVISED
 2020 FBC-RESIDENTIAL TABLE. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 11- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS.
 REVISED NAIL SPACING TO COMPLY TABLE R803.2.3.1
 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 B)FAMILY ROOM SECTIONAL DOORS THAT MEET THE CALCULATED
 DESIGN PRESSURES. FLORIDA PRODUCT APPROVAL FL27023-R1
 SUBMITTED DOESN'T MEET THOSE PRESSURES.
 NOTE: PRODUCT APPROVAL SUBMITTED IS FOR NON-IMPACT
 DOORS. HURRICANE SHUTTERS PRODUCT APPROVAL AND COMPLETE
 INSTALLATION SCHEDULE WILL BE REQUIRED.
  
 C)FIXED WINDOW TYPE "C" AS SHOWN ON PLANS.
  
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY DESIGN PRESSURES. SEC. R301.2.1
 FBC-RESIDENTIAL).
  
 E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. AND, CLEARLY
 SPECIFY SELECTED ASSEMBLY TO BE INSTALLED.
  
 F)HIP & RIDGE METAL SUPPORT TO BE USED FOR ROOF TILES.
  
 G)ROOF TILE NOA SUBMITTED: CLEARLY SPECIFY ADHESIVE
 PARTY SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS TO VERIFY UPLIFT. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 H)ROOF TILE ADHESIVE LISTED ON THE ROOF TILE NOA AND
 SPECIFY PADDY SIZE.
  
 NOTE FOR FLORIDA PRODUCT APPROVALS SUBMITTALS:
 PLEASE DON'T SEPARATE THE PRODUCT APPROVAL. COMPLETE
 PRODUCT APPROVAL (FLORIDA PRODUCT APPROVAL COVER PAGE
 AND INSTALLATION INSTRUCTIONS) SHOULD BE UPLOADED IN
 THE SAME PDF FILE FOR EACH PRODUCT.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- PROVIDE SURVEY SHOWING THE PROPOSED HOUSE AS
 REQUIRED BY SEC. 107.2.5 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE AUDIT PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]