Plan Review Notes
Plan Review Notes For Permit 22010180
Permit Number 22010180
Review Stop G
Sequence Number 1
Notes
Date Text
2022-04-09 11:59:50PLAN REVIEW / FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A GAS SUB-PERMIT IS REQUIRED.
  
 1. PIPE SIZES TO THE 199,000 BTU TANKLESS W/H AND THE
 90,000 BTU GRILL APPEAR TO BE INCORRECT. RE-CALCULATE
 THE SIZE OF EACH PIPE USING THE LONGEST RUN METHOD AND
 TABLE 402.4(2).
  
 2. SUBMIT APPLICABLE GAS TABLES. TABLE 402.4(2).
  
 3. SUBMIT MANUFACTURERS SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 4. IF REQUIRED BASED ON LINE PRESSURE -VS- APPLIANCE
 DEMAND PRESSURE, SUBMIT LOW PRESSURE GAS REGULATOR
 SPECIFICATIONS. 2020 FBC FUEL GAS SEC.305.1 OR 2020 FBC
 FUEL GAS RES. SEC. G2408.1.
  
 NOTICE: REGULATORS SHALL HAVE A UNION INSTALLED WITHIN
 1 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2
  
 NOTICE: REGULATORS SHALL BE LOCATED PER 409.1.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  