Plan Review Notes
Plan Review Notes For Permit 22010180
Permit Number 22010180
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-09 10:09:15PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEE PLAN PAGES P1 AND P2 FOR ROOF DRAINAGE PLAN FOR
 THE FLAT ROOFS.
 PROVIDE CALCULATION TO DETERMINE SIZE AND LOCATION OF
 2ND FLOOR FLAT ROOF DRAINS.
 PROPOSED DRAIN TO BE A ZURN MODEL #Z1786-6" SS DRAIN.
 PROVIDE SPECIFICATIN SHEET FOR DRAIN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 R903.4ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF.
 R903.4.1OVERFLOW DRAINS AND SCUPPERS.
 R903.4.2ONE AND TWO-FAMILY DWELLINGS, AND PRIVATE
 GARAGES.
  
 2. SEE PLAN PAGES S10 & S11 FOR THE FOLLOWING: PROVIDE
 THE WINDOW AND DOOR (W/D) TYPE FROM THE W/D SCHEDULE
 NEXT TO EACH OPENING.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. IDENTIFY THE EXTERIOR WALL INSULATION TYPE AND R
 VALUE ON THE PLANS. WALL INSULATION R VALUE FROM THE
 ENERGY SUBMITTAL IS R-4.1.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE THE ICC-ES REPORT FOR THE PROPOSED ICYNENE
 SPRAY FOAM INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 5. FINISHED FLOOR ELEVATION. SEE PLAN PAGES SP1.0 AND
 CO.1 FOR THE FOLLOWING:
 NOTE ON PG SP1.0 STATES "1ST FLOOR TOP OF SLAB, EL.
 VERIFY B.F.E". THIS PROPERTY IS NOT LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (SFHA). FEMA HAS NOT
 ESTABLISHED A BASE FLOOD ELEVATION (B.F.E.).
 REMOVE REFERENCE TO B.F.E. ON PG SP1.0.
 FINISHED FLOOR ELEVATION IS STATED AS 11.75 NAVD ON PG
 CO.1.
 FINISH FLOOR ELEVATION NON-FLOOD ZONE
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 6. LANDSCAPE EDGING: SEE SITE DRAINAGE PLAN CO.1 AND
 DETAILS 1/'CO.1 AND 2/CO.1 FOR THE FOLLOWING:
 DESCRIPTION: CORTEN STRUCTURAL COMPONENTS ASTM A606-4
 WEATHERING STEEL, 11 GUAGE, 12" WIDE LANDSCAPE EDGING,
 TO BE INSTALLED ALONG THE SOUTH AND WEST PROPERTY LINES
 TO PREVENT CROSS-DRAINAGE WITH THE NEIGHBORS
 PROPERTIES.
 6A) PROVIDE A COPY OF ASTM A606-4.
 6B) PROVIDE PRODUCT SPECIFICATIONS.
 6C) PROVIDE TOPO. ELEVATIONS: TOP OF GRADE (TOG) ALONG
 INSIDE OF EDGING AND TOG ALONG ADJOINING PROPERTIES.
 6D) PROVIDE TOP OF EDGING (TOE) ELEVATIONS.
 6E) PROVIDE SOIL EMBEDMENT DETAIL OF EDGING WITH
 DEMENSIONS.
  
 NOTICE:
  
 PROVISO FOR SITE WALLS WITH GATES SHOWN ON PLAN PAGE
 SP-1.0. A SEPERATE PERMIT IS REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  