2022-03-21 17:11:54 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22010129 |
| 3/21/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. REMAINING 1ST REVIEW |
| COMMENTS LISTED BELOW. |
| |
| 1) FAILED. SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING |
| FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC |
| P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY |
| WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET |
| C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT |
| DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY |
| AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE |
| REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE |
| DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE |
| PROVIDED- SEC.- 410.4 FBC P. THE CORRECTED C-1 SHEET |
| WAS NOT UPLOADED. |
| |
| 3) FAILED. SHEET 1.0A- MISSING ACCESSIBILITY DETAILS |
| PER FBC ACC: |
| K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC. |
| 605.2. NOT PROVIDED. |
| L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| ACCESSIBLE URINAL- SEC. 605.3. NOT PROVIDED. |
| |
| 4) FAILED. SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS |
| OF THE STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P. |
| NOT PROVIDED. |
| |
| |
| 5) FAILED. SHEET 3.0P: PROVIDE GREASE WASTE |
| CALCULATIONS IN COMPLIANCE WITH SEC. 1003.3.5 FBC P. |
| PLEASE ADD THE GREASE INTERCEPTOR TO THE LIST OF |
| SEPARATE PERMITS ON SHEET C-1. NOTE: COMPLETE GREASE |
| INTERCEPTOR PLANS, EQUIPMENT SPECIFICATIONS, |
| CALCULATIONS AND DETAILS WILL BE REQUIRED UNDER THE |
| SEPARATE PERMIT. CORRECTED SHEET 3.0P NOT UPLOADED. |
| |
| 12) FAILED. SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE |
| PERMIT IS REQUIRED FOR THE POTABLE WATER SERVICE |
| BACKFLOW PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE |
| ADD THE DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET |
| C-1. SHEET C-1 WITH MODIFED SEPARATE PERMIT LIST NOT |
| UPLOADED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |