Plan Review Notes
Plan Review Notes For Permit 22010129
Permit Number 22010129
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-21 17:11:542ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22010129
 3/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. REMAINING 1ST REVIEW
 COMMENTS LISTED BELOW.
  
 1) FAILED. SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING
 FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY
 WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET
 C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT
 DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY
 AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE
 REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE
 DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE
 PROVIDED- SEC.- 410.4 FBC P. THE CORRECTED C-1 SHEET
 WAS NOT UPLOADED.
  
 3) FAILED. SHEET 1.0A- MISSING ACCESSIBILITY DETAILS
 PER FBC ACC:
 K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC.
 605.2. NOT PROVIDED.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE URINAL- SEC. 605.3. NOT PROVIDED.
  
 4) FAILED. SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS
 OF THE STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P.
 NOT PROVIDED.
  
  
 5) FAILED. SHEET 3.0P: PROVIDE GREASE WASTE
 CALCULATIONS IN COMPLIANCE WITH SEC. 1003.3.5 FBC P.
 PLEASE ADD THE GREASE INTERCEPTOR TO THE LIST OF
 SEPARATE PERMITS ON SHEET C-1. NOTE: COMPLETE GREASE
 INTERCEPTOR PLANS, EQUIPMENT SPECIFICATIONS,
 CALCULATIONS AND DETAILS WILL BE REQUIRED UNDER THE
 SEPARATE PERMIT. CORRECTED SHEET 3.0P NOT UPLOADED.
  
 12) FAILED. SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE
 PERMIT IS REQUIRED FOR THE POTABLE WATER SERVICE
 BACKFLOW PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE
 ADD THE DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET
 C-1. SHEET C-1 WITH MODIFED SEPARATE PERMIT LIST NOT
 UPLOADED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  