Date |
Text |
2022-03-21 17:10:50 | 2ND REVIEW FBC-2020 FUEL GAS |
| PERMIT- 22010129 |
| 3/21/2022 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. REMAINING COMMENTS FROM |
| THE 1ST REVIEW ARE LISTED BELOW. |
| |
| 1) FAILED. SHEET 3.0P GAS RISER: INCREASE THE 1-INCH |
| PIPE SHOWN AT THE 33 FT. RUN TO 1-1/2-INCH BASED ON |
| TABLE 402.4(2) FBC FG. CORRECTED SHEET 3.0P NOT |
| UPLOADED. |
| |
| 2) FAILED. SHEET 3.0P GAS RISER: SHOW THE BRANCH PIPE |
| SIZES FOR THE APPLIANCES ON THE COOKING LINE- TABLE |
| 402.4(2) FBC FG. SHEET 3.1P SHOWS INDIVIDUAL COMBUSTION |
| AIR INTAKE AND EXHAUST DUCTS. ALL OTHER PLANS INDICATE |
| A CONCENTRIC VENT- WHICH IS IT? |
| |
| 4) FAILED. SHEET 3.0P: PROVIDE A VENTING DIAGRAM FOR |
| THE TANKLESS WATER HEATER SHOWING THE TYPE AND SIZE OF |
| CONCENTRIC, VENT RUN LENGTH FROM THE APPLIANCE TO THE |
| TERMINATION ABOVE THE ROOF, CLEARANCE HEIGHT ABOVE THE |
| ROOF, AND CLEARANCES TO AIR EXHAUST OUTLET AND AIR |
| INTAKES ON THE ROOF- SECS. 503.2.3, 503.8 & 624.1. A) |
| SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CONCENTRIC |
| VENT DUCT- SECS. 503.4.1 & 624.1 FBC FG. PLEASE NOTE |
| THE VENT DUCT SHALL BE LISTED AND LABELED PER SEC. |
| 503.3.6: |
| |
| WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING |
| AIR-HANDLING SPACE OR OTHER NON-DUCTED PORTION OF AN |
| AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM |
| TO ONE OF THE FOLLOWING REQUIREMENTS: |
| |
| 1.THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS |
| VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR |
| CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT, |
| WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR |
| VENT MANUFACTURER?S INSTRUCTIONS. |
| 2.THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT |
| FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED |
| IN THE ABOVE-CEILING SPACE. |
| 3.THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT OR |
| ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR OF |
| THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE. VENT |
| SPECS NOT SUBMITTED |
| |
| 6) FAILED. SHEET 3.0P: THE PLAN SHOWS A GAS-FIRED |
| TANKLESS WATER HEATER ON THE EXTERIOR WALL. IS THIS |
| HEATER IN USE OR TO BE REMOVED- SEC. 107.2.1 WPB. |
| CORRECTED SHEET 3.0P NOT UPLOADED. |
| |
| 7) FAILED. SHEET 3.0P: PROVIDE A CONDENSATE DISPOSAL |
| PLAN FOR THE NEW INTERIOR GAS-FIRED WATER HEATER- SECS. |
| 307.2, 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF |
| CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN |
| LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING |
| DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. CORRECTED |
| SHEET 3.0P NOT UPLOADED. PLEASE NOTE THAT CONDESNATE |
| SHALL NOT DRAIN INTO THE SANITARY SYSTEM- SEC. 90-126 |
| WPB CODE OF ORDINANCES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| CCOLE@WPB. |
| |