Plan Review Notes
Plan Review Notes For Permit 22010129
Permit Number 22010129
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-20 17:43:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22010129
 1/20/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY
 WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET
 C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT
 DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY
 AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE
 REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE
 DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE
 PROVIDED- SEC.- 410.4 FBC P.
  
 2) SHEETS 1.0A, 1.3A, 3.0P, 3.1P: SHEET 1.3A INDICATES
 A 1390 SQ. FT. BREWERY. SHOW THE LOCATION OF THE
 BREWERY AND PROVIDE AN EQUIPMENT PLAN AND SCHEDULE-
 SEC. 107.2.1 WPB.
  
 3) SHEET 1.0A- MISSING ACCESSIBILITY DETAILS PER FBC
 ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC.
 605.2
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE URINAL- SEC. 605.3.
 M) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2
  
 4) SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS OF THE
 STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P.
  
 5) SHEET 3.0P: PROVIDE GREASE WASTE CALCULATIONS IN
 COMPLIANCE WITH SEC. 1003.3.5 FBC P. PLEASE ADD THE
 GREASE INTERCEPTOR TO THE LIST OF SEPARATE PERMITS ON
 SHEET C-1. NOTE: COMPLETE GREASE INTERCEPTOR PLANS,
 EQUIPMENT SPECIFICATIONS, CALCULATIONS AND DETAILS WILL
 BE REQUIRED UNDER THE SEPARATE PERMIT.
  
 6) SHEETS 3.0P & 3.1P: SHOW THE LOCATION OF THE GREASE
 INTERCEPTOR SAMPLING PORT AND INDICATE ACCESS WILL BE
 PROVIDED TO THE INTERCEPTOR COVERS AND CLEANOUTS- SECS.
 708.1.7 & 708.1.10 FBC P.
  
 7) SHEET 3.0P: THE LOCATION OF THE FLOOR SINK IN THE
 DETAIL DOES NOT MATCH THE LOCATION ON THE PLAN. THE
 PLAN SHOWS THE FLOOR SINK BETWEEN THE FOOD HANDLING
 (3-COMPARTMENT) SINK AND THE WARE WASHER- SEC. 802.1.1
 AND 802.3 FBC P. PLEASE INCLUDE THE FLOOR SINKS IN THE
 PLUMBING FIXTURE SCHEDULE- SECS. 414.1 & 802.4 FBC P.
  
 8) SHEETS 3.0P & 3.1P: PROVIDE VENTS FOR THE FLOOR
 SINKS AND FLOOR DRAINS IN THE KITCHEN AREA- SEC. 802.3
 FBC P AND THE FLOOR DRAIN IN THE MEN'S RESTROOM- SECS.
 910 & 911 FBC P.
  
 9) SHEETS 3.0P & 3.1P: THE PLAN SHOWS 3/4-INCH SUPPLY
 LINES TO THE URINALS, AND THE RISER SHOWS 1-INCH- SEC.
 107.2.1 WPB. PLEASE NOTE A COMPLETE REVIEW OF THE
 PLUMBING PLANS CANNOT BE COMPLETED WITH A PLUMBING
 FIXTURE SCHEDULE- TABLE 604.5 FBC P.
  
 10) SHEETS 3.0P & 3.1P: SHOW LOCATIONS OF REQUIRED
 BACKFLOW PREVENTERS FOR SUPPLY LINES CONNECTING TO THE
 WARE WASHER, GLASS WASHER, AND ICE MAKERS- SEC. 608.3
 FBC P.
  
 11) SHEETS 3.0P & 3.1P: A RECIRCULATION PUMP IS SHOWN
 BUT THERE IS A NOTE INDICATING A RECIRCULATING WATER
 HEATER. WHICH RECIRCULATION SYSTEM WILL BE USED?- SEC.
 607.1 FBC P.
  
 12) SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE ADD THE
 DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET C-1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  