Plan Review Notes
Plan Review Notes For Permit 22010129
Permit Number 22010129
Review Stop G
Sequence Number 1
Notes
Date Text
2022-01-20 17:38:181ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22010129
 1/20/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.0P GAS RISER: INCREASE THE 1-INCH PIPE SHOWN
 AT THE 33 FT. RUN TO 1-1/2-INCH BASED ON TABLE 402.4(2)
 FBC FG.
  
 2) SHEET 3.0P GAS RISER: SHOW THE BRANCH PIPE SIZES FOR
 THE APPLIANCES ON THE COOKING LINE- TABLE 402.4(2) FBC
 FG.
  
 3) SHEET 3.0P: CORRECT THE COMBUSTION AIR CALCULATION
 TO INDICATE .35 X473 KBTUH- SEC. 304.9 FBC P. CLARIFY
 HOW THE 165 CFMS OF COMBUSTION AIR IS BEING PROVIDED
 MECHANICALLY. THE O/A CALCULATIONS ON SHEET 4.0M
 INDICATE A TOTAL OF 190 CFMS FOR THE OCCUPANTS- SEC.
 304.9.3 FBC FG.
  
 4) SHEET 3.0P: PROVIDE A VENTING DIAGRAM FOR THE
 TANKLESS WATER HEATER SHOWING THE TYPE AND SIZE OF
 CONCENTRIC, VENT RUN LENGTH FROM THE APPLIANCE TO THE
 TERMINATION ABOVE THE ROOF, CLEARANCE HEIGHT ABOVE THE
 ROOF, AND CLEARANCES TO AIR EXHAUST OUTLET AND AIR
 INTAKES ON THE ROOF- SECS. 503.2.3, 503.8 & 624.1. A)
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CONCENTRIC
 VENT DUCT- SECS. 503.4.1 & 624.1 FBC FG. PLEASE NOTE
 THE VENT DUCT SHALL BE LISTED AND LABELED PER SEC.
 503.3.6:
  
 WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING
 AIR-HANDLING SPACE OR OTHER NON-DUCTED PORTION OF AN
 AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM
 TO ONE OF THE FOLLOWING REQUIREMENTS:
  
 1.THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS
 VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR
 CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT,
 WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR
 VENT MANUFACTURER?S INSTRUCTIONS.
 2.THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT
 FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED
 IN THE ABOVE-CEILING SPACE.
 3.THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT OR
 ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR OF
 THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE.
  
 5) SHEET 3.0P: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE COOKING APPLIANCES- SEC. 623.1 FBC FG.
  
 6) SHEET 3.0P: THE PLAN SHOWS A GAS-FIRED TANKLESS
 WATER HEATER ON THE EXTERIOR WALL. IS THIS HEATER IN
 USE OR TO BE REMOVED- SEC. 107.2.1 WPB.
  
 7) SHEET 3.0P: PROVIDE A CONDENSATE DISPOSAL PLAN FOR
 THE NEW INTERIOR GAS-FIRED WATER HEATER- SECS. 307.2,
 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved