Plan Review Notes
Plan Review Notes For Permit 22010109
Permit Number 22010109
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-25 15:48:57PROVISO:
 1- SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR. WINDOW OPENING CONTROL DEVICES NEED TO
 COMPLY WITH ASTM F2090.
 NOTE: THIS SECTION ALSO APPLIES TO OPERABLE WINDOWS
 WHERE WINDOW SILL IS GREATER THAN 72 INCHES ABOVE GRADE
 OR OTHER SURFACE BELOW.
  