2022-06-30 14:33:20 | NFIP REVIEW: |
| |
| 1- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD |
| ZONE WITH THE BASE FLOOD BFE: 6 & 7 FEET BASED ON NAVD |
| 1988. |
| CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2) |
| FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC. |
| 18-284 CITY ORDINANCE NO. 4729-17). NEED TO SPECIFY THE |
| PROPOSED FINISHED FLOOR ELEVATION IN ALL FLOOR PLANS |
| BASED ON NAVD 1988. |
| DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT |
| FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED (SEC. |
| 107.3.5.1.1 CITY AMENDMENTS): |
| A) CONSTRUCTION DRAWINGS. |
| B) BUILDING UNDER CONSTRUCTION. |
| C) FINISHED CONSTRUCTION. |
| NOTE: |
| NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION |
| CERTIFICATE NOW FOR REVIEW. |
| |
| RESPONSE: |
| ELEVATION CERTIFICATE SUBMITTED IS FOR THE MAIN |
| RESIDENCE. NEED TO PROVIDE THE CONSTRUCTION DRAWINGS |
| ELEVATION CERTIFICATE FOR THE PROPOSED BUILDING. |
| NOTE: FLOOD VENTS ARE REQUIRED FOR GARAGE AND EXISTING |
| STORAGE/SHED. REVISE PLANS AS REQUIRED. |
| ALSO, CLARIFY IF USING ENGINEERED FLOOD VENTS OR |
| NON-ENGINEERED FLOOD VENTS. IF USING ENGINEERED FLOOD |
| VENTS, THEN PROVIDE PRODUCT APPROVAL (IT MAY BE |
| DEFERRED) AND WRITE STATEMENT REQUIRED BY SEC. R322.2.2 |
| FBC-RESIDENTIAL. |
| IF USING NON-ENGINEERED VENTS, THEN NEED TO PROVIDE |
| COMPLETE DETAILS/SPECIFICATIONS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| |