2022-03-10 16:04:41 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22010026 |
| |
| 1-THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD ZONE |
| WITH THE BASE FLOOD BFE: 6 & 7 FEET BASED ON NAVD 1988. |
| CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2) |
| FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC. |
| 18-284 CITY ORDINANCE NO. 4729-17). NEED TO SPECIFY THE |
| PROPOSED FINISHED FLOOR ELEVATION IN ALL FLOOR PLANS |
| BASED ON NAVD 1988. SEC.107.3.5.3 CITY AMENDMENTS. |
| NOTE: IF THE GARAGE FINISH FLOOR ELEVATION IS BELOW THE |
| BFE (BASE FLOOD ELEVATION) PLUS TWO FEET, THEN FLOOD |
| VENTS WILL BE REQUIRED. SEC. R322.2.2 FBC-RESIDENTIAL. |
| |
| NOTE: DURING THE PERMITTING OF THIS STRUCTURE THREE |
| DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED |
| (SEC. 107.3.5.1.1 CITY AMENDMENTS): |
| A) CONSTRUCTION DRAWINGS. |
| B) BUILDING UNDER CONSTRUCTION. |
| C) FINISHED CONSTRUCTION. |
| |
| NOTE: |
| NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION |
| CERTIFICATE NOW FOR REVIEW. |
| |
| 2- PROVIDE CURRENT SURVEY SHOWING PROPOSED ADDITION AND |
| FINISHED FLOOR ELEVATION INCLUDING THE FINISHED FLOOR |
| ELEVATION OF THE EXISTING BATH HOUSE. SEC.107.3.5.3 |
| CITY AMENDMENTS. |
| NOTE: EXISTING BATH HOUSE FINISHED FLOOR WILL NEED TO |
| BE RAISED IF IT IS BELOW THE BFE (BASED FLOOD |
| ELEVATION) PLUS 2 FEET. |
| |
| 3-PROPOSED WORK AFFECTS THE LOT DRAINAGE, SPECIALLY ON |
| THE WEST SIDE WHERE THERE IS ONLY A 5 FOOT SETBACK. |
| PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE |
| IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT |
| PROPERTY. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS. |
| |
| SITE PLAN ON SHEET SP-1 SPECIFIES A RETAINING WALL ON |
| THE WEST SIDE. A SEPARATE PERMIT IS REQUIRED FOR THE |
| CONSTRUCTION OF THIS WALL. SEC. 105.1 CITY AMENDMENTS. |
| NOTE: CLEARLY INDICATE ON PLAN THE EXTEND OF RETAINING |
| WALL AND PROVIDE STRUCTURAL DETAIL OF WALL. HOW IS THE |
| STACKED BLOCK REINFORCED TO STAY IN PLACE. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| NOTE: |
| THIS PROPERTY IS LOCATED IN FLOOD ZONE AE. KEEP IN MIND |
| REQUIRED FINISHED FLOOR ELEVATION WHEN DESIGNING THE |
| DRAINAGE PLAN. COORDINATE WITH ITEM #1 AND #2 ABOVE. |
| |
| 4- THERE IS A CONFLICT ON THE LIVE AND DEAD LOADS |
| SPECIFIED ON SHEET SP-1. |
| LOADS SPECIFIED UNDER MINIMUM SOIL BEARING CAPACITY |
| DON'T MATCH LOADS SPECIFIED UNDER GRAVITY DESIGN |
| LOADINGS FOR THIS PROJECT ON SAME SHEET. REVISE AS |
| REQUIRED TO MATCH. NOTE: COORDINATE WITH INFORMATION |
| SHOWN ON SHEET S-0 ALSO TO AVOID CONFLICTS/DELAYS. |
| CLEARLY SPECIFY ALL LIVE AND DEAD LOADS FOR SECOND |
| FLOOR AND ROOF. CLEARLY SPECIFY SECOND FLOOR LIVE AND |
| DEAD LOADS (TOP AND BOTTOM CHORDS) AND ROOF LIVE AND |
| DEAD LOADS (TOP AND BOTTOM CHORDS), INCLUDING THE ATTIC |
| LIVE LOAD AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. |
| SEE FOOTNOTES "B" AND "G". |
| |
| 5- DESIGN PRESSURES SPECIFIED ON SHEET S-0 AND SHEET |
| SP-1 ARE LOW FOR WORST CASE CONDITION. SEE SPECIFIED |
| EXPOSURE AND HEIGHT AND REVISE AS REQUIRED. TABLE |
| R301.2(2) FBC-RESIDENTIAL. |
| |
| 6- PROVIDE COMPLETE WALL SECTION (FOOTING TO ROOF) FOR |
| STRUCTURAL SUPPORT OF THE SECOND FLOOR BY THE EXISTING |
| BATH HOUSE SHOWING THE LOAD PATH. SEC. R601.2 |
| FBC-RESIDENTIAL. COORDINATE WITH PILE & GRADE BEAM |
| PLAN, FOUNDATION PLAN AND 2ND FLOOR FRAMING PLAN ON |
| SHEET S-1. |
| NOTE: ENGINEER OF RECORD TO SPECIFY SIZE OF EXISTING |
| FOOTING AND VERIFY IF IT IS ADEQUATE TO SUPPORT THE |
| ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 7- 2ND FLOOR FRAMING PLAN DOESN'T SPECIFY THE DEPTH OF |
| THE FLOOR TRUSSES. PROVIDE INFORMATION. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 8- IT LOOKS LIKE THE ROOF OF THE EXISTING BATH HOUSE |
| NEEDS TO BE CUT TO RECEIVE THE WALL OF THE SECOND FLOOR |
| ADDITION. PROVIDE INFORMATION OF HOW THE EXISTING ROOF |
| JOISTS/TRUSSES ARE REINFORCED/REFRAMED. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| DWELLING- GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| R302.6 FBC-RESIDENTIAL AND TABLE R302.6 |
| FBC-RESIDENTIAL. |
| |
| 10- PROVIDE COMPLETE STRUCTURAL BUCK DETAIL AND |
| FASTENING SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 11--WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE IF THERE IS ANY THE WINDOW SILL |
| HEIGHT LESS THAN 24" ABOVE THE FINISHED FLOOR. SPECIFY |
| TYPE OF WINDOW FALL PROTECTION IF REQUIRED. |
| |
| 12- BUILDING IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT |
| IS SPECIFYING R-20 ICYNENE SPRAY INSULATION. PROVIDE |
| ICC EVALUATION REPORT FOR THE ICYNENE R-20 INSULATION |
| TO VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| 13-ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE, |
| JURISDICTION (THIS JURISDICTION IS 604700). SEC. |
| R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| B)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| C)ROOF TYPE SPECIFIED ON PAGE 2 DOESN'T MATCH PLANS. |
| THIS IS A GABLE ROOF NOT HIP. REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| D)REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 TO |
| MATCH PLANS. REVISE OVERHANG SEPARATION TO MATCH |
| EXTERIOR ELEVATIONS. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| 14- ARCHITECT NEEDS TO DEPICT THE BUILDING THERMAL |
| ENVELOPE AND SPECIFY INSULATION MATERIALS AND THEIR |
| R-VALUES. NEED TO SPECIFY THE THERMAL INSULATION |
| BETWEEN GARAGE AND A/C AREA ABOVE. SEC. R103.2 |
| FBC-ENERGY CONSERVATION. |
| |
| 15-DEFERRED PRODUCT APPROVALS: |
| (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| A)EXTERIOR DOORS. |
| B)WINDOWS. |
| C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| D)DECORATIVE SHUTTERS AND SPECIFY FASTENING. |
| E)ROOF TILE AND CLEARLY SPECIFY ROOF TILE FASTENING |
| METHOD. |
| F) ROOF TILE ADHESIVE (IF USED) AND CLEARLY SPECIFY |
| PADDY SIZE. |
| G)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED. |
| CLEARLY MARK WHICH ONE WILL BE USED. |
| |
| 16- DEFERRED SUBMITTAL: |
| GUARDRAILS AND HANDRAILS. |
| (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. INFORMATION TO |
| BE APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL). |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |