Plan Review Notes For Permit 21121225 |
Permit Number |
21121225 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2022-05-16 14:07:02 | BUILDING REVIEW APPROVED WITH PROVISO: | | (NOTE: SUBMIT INFORMATION PRIOR TO | | INSTALLATION/INSPECTION TO AVOID CONFLICTS/DELAYS): | | | | 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE | | CONSTRUCTION OF ALL HANDRAILS AND GUARDRAILS SHOWING | | COMPLIANCE WITH TABLE R301.5, SEC. R311.7.8 AND SEC. | | R312.1 FBC-RESIDENTIAL. | | | | 2- WINDOW FALL PROTECTION IS REQUIRED ON SECOND FLOOR | | OPERABLE WINDOWS WHERE WINDOW SILL IS LESS THAN 24" | | ABOVE FINISHED FLOOR. SEC. R312.2 FBC RESIDENTIAL. | | NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT AND | | SPECIFY TYPE OF WINDOW FALL PROTECTION IF REQUIRED. | | | | 3- PRODUCT APPROVALS: | | PROVIDE PRODUCT APPROVAL FOR FIXED WINDOW SIZE 74"X180" | | AS SHOWN ON PLANS. | | | | 4-ENGINEER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT | | APPROVALS. | | |
|