Plan Review Notes
Plan Review Notes For Permit 21121220
Permit Number 21121220
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-29 16:32:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121220 4920 LORING DR
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.NEW COMMENT: DUE TO A CHANGE IN PROCESS, THE BACKFLOW
 PERMIT AND GREASE INTERCEPTOR PERMITS ARE REQUIRED TO
 BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT
 (AS APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD"
 (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 2.NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL FOR
 SINK SHOWING HEIGHT, KNEE AND TOE SPACE. FRONT APPROACH
 FOR SINK IS SHOWN ON A1. COMPLY WITH FBC ACC 606.3,
 306.2 AND 306.3.
  
 3. SECOND REQUEST: MATERIAL SPEC PER WPB FBC 107.2.1,
 PROVIDE PIPING MATERIAL SPEC FOR EACH SYSTEM TO INCLUDE
 PIPE, VALVES, FITTINGS AND JOINTS. COMPLY WITH FBC PL
 CHAPTERS 3, 6, 7, 9 AND 11.
 PROVIDE SPECIFICATION 22 10 00 AS NOTED IN RESPONSE.
  
 4.NEW COMMENT: A VENT IS REQUIRED FOR THE EXISTING
 FLOOR DRAIN PER FBC PL 901.2.1.
  
 5.NEW COMMENT: PLEASE NOTE THAT PER FBC PL 301.7 AND
 303.2, THE INSTALLATION OF THE SCHIER GB-75 GREASE
 INTERCEPTOR SHALL CONFORM TO A MINIMUM OF THE
 MANUFACTURER?S RECOMMENDATIONS. IN ACCORDANCE WITH THE
 GB-75 INSTALLATION MANUAL, A TWO-WAY CLEANOUT IS
 REQUIRED ON THE INLET AND OUTLET SIDE OF THE GREASE
 INTERCEPTOR.
  
 6. NEW COMMENT: PER WPB FBC 107.2.1, TO SHOW COMPLIANCE
 WITH FBC PL 409.4, PROVIDE A NOTE ON P-4/DISHWASHING
 CONNECTION STATING "THE WASTE CONNECTION OF A
 RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE
 BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK,
 DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE
 DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE
 WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER TOP."
  
 7.SECOND REQUEST: A WATER HAMMER ARRESTOR IS REQUIRED
 ON THE HOT WATER TO THE DISHWASHER PER FBC PL 604.9.
 PER WPB FBC 107.2.1, PROVIDE A WATER HAMMER ARRESTOR
 FOR THE HOT WATER TO THE DISHWASHER. THIS MAY BE
 ACCOMPLISHED BY PROVIDING A NOTE ON P-4/DISHWASHING
 CONNECTION.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS