2022-03-29 16:32:50 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21121220 4920 LORING DR |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1.NEW COMMENT: DUE TO A CHANGE IN PROCESS, THE BACKFLOW |
| PERMIT AND GREASE INTERCEPTOR PERMITS ARE REQUIRED TO |
| BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT |
| (AS APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" |
| (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| |
| 2.NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL FOR |
| SINK SHOWING HEIGHT, KNEE AND TOE SPACE. FRONT APPROACH |
| FOR SINK IS SHOWN ON A1. COMPLY WITH FBC ACC 606.3, |
| 306.2 AND 306.3. |
| |
| 3. SECOND REQUEST: MATERIAL SPEC PER WPB FBC 107.2.1, |
| PROVIDE PIPING MATERIAL SPEC FOR EACH SYSTEM TO INCLUDE |
| PIPE, VALVES, FITTINGS AND JOINTS. COMPLY WITH FBC PL |
| CHAPTERS 3, 6, 7, 9 AND 11. |
| PROVIDE SPECIFICATION 22 10 00 AS NOTED IN RESPONSE. |
| |
| 4.NEW COMMENT: A VENT IS REQUIRED FOR THE EXISTING |
| FLOOR DRAIN PER FBC PL 901.2.1. |
| |
| 5.NEW COMMENT: PLEASE NOTE THAT PER FBC PL 301.7 AND |
| 303.2, THE INSTALLATION OF THE SCHIER GB-75 GREASE |
| INTERCEPTOR SHALL CONFORM TO A MINIMUM OF THE |
| MANUFACTURER?S RECOMMENDATIONS. IN ACCORDANCE WITH THE |
| GB-75 INSTALLATION MANUAL, A TWO-WAY CLEANOUT IS |
| REQUIRED ON THE INLET AND OUTLET SIDE OF THE GREASE |
| INTERCEPTOR. |
| |
| 6. NEW COMMENT: PER WPB FBC 107.2.1, TO SHOW COMPLIANCE |
| WITH FBC PL 409.4, PROVIDE A NOTE ON P-4/DISHWASHING |
| CONNECTION STATING "THE WASTE CONNECTION OF A |
| RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE |
| BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK, |
| DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE |
| DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE |
| WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND |
| BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| OR COUNTER TOP." |
| |
| 7.SECOND REQUEST: A WATER HAMMER ARRESTOR IS REQUIRED |
| ON THE HOT WATER TO THE DISHWASHER PER FBC PL 604.9. |
| PER WPB FBC 107.2.1, PROVIDE A WATER HAMMER ARRESTOR |
| FOR THE HOT WATER TO THE DISHWASHER. THIS MAY BE |
| ACCOMPLISHED BY PROVIDING A NOTE ON P-4/DISHWASHING |
| CONNECTION. |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |