Date |
Text |
2022-04-04 18:41:32 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NOT RESOLVED. [ SHEET A-3 THE INTERIOR ELEVATIONS |
| WAS NOT UPLOADED. PLAN SHEET A-4, THE ACCESSIBILITY |
| DETAILS, IS UPLOADED UNDER PAGE 007 A-3. SHEET ID-1 IS |
| INCORRECTLY UPLOADED UNDER PAGE 008 A-4. SHEET ID-1 WAS |
| UPLOADED TWICE. PAGES 008 AND 009 BOTH HAVE PLAN SHEET |
| ID-1 UPLOADED. ] THE KITCHEN ELEVATIONS 1,2,3 & 4 THAT |
| ARE TAGGED ON THE FLOOR PLAN ON SHEET A1 AS BEING ON |
| SHEET A2 ARE MISSING. THE COUNTER TOP HEIGHTS AND REACH |
| RANGES ARE REQUIRED TO COMPLY WITH THE 2020 FBC |
| ACCESSIBILTY. FBC 107.2.1 |
| |
| 2) NEW COMMENT. ON THE LIFE SAFETY PLAN PAGE 003 LS-1 |
| THE KITCHEN AREA IS SHOWN AS LARGER THAN THE ACTUAL |
| KITCHEN AREA. IT APPEARS THIS IS BEING DONE TO REDUCE |
| THE SIZE OF THE DINING/ASSEMBLY AREA. THE KITCHEN AREA |
| NEEDS TO BE LIMITED TO THE AREA WHERE THE FOOD |
| PREPARATION AND OTHER KITCHEN ACTIVITIES WILL ACTUALLY |
| OCCUR. ALSO NOTE THAT FBC 1016.2 (5) PROHIBITS EXIT |
| ACCESS THROUGH KITCHENS. |
| |
| 3) THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING: |
| A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 |
| B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 |
| C) EXIT SEPARATION DISTANCE FBC 1015.2.1 |
| D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 |
| E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 |
| F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC |
| 1008.1.1 |
| G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND |
| MEANS OF EGRESS FACTOR FBC1005.3.2 |
| H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 |
| |
| 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. NOTE: |
| ADDITIONAL COMMENTS MAY RESULT WHEN THE MISSING |
| INFORMATION IS PROVIDED. |