Plan Review Notes For Permit 21121220 |
Permit Number |
21121220 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-24 13:41:45 | FIRE PROVISO NOTES:(FAIL) | | 1. COOKING EQUIPMENT USED IN PROCESSES PRODUCING SMOKE | | OR GREASE LADEN VAPORS SHALL BE EQUIPPED WITH AN | | EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND | | PERFORMANCE REQUIREMENTS OF THIS STANDARD. NFPA 96, | | 4.1.1 | | COOKING EQUIPMENT THAT PRODUCES GREASE LADEN VAPORS AND | | THAT MIGHT BE AA SOURCE OF IGNITION OF GREASE IN THE | | HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE PROTECTED | | BY FIRE-EXTINGUISHING EQUIPMENT. NFPA 96, 10.1.2 | | FOR CLARIFICATION AND THE OFFICIAL RECORD, PROVIDE A | | DETAILED DESCRIPTION OF THE USE THE DEMONSTRATION | | KITCHEN. | | | | 2. ALL FIRE SPRINKLER AND/OR FIRE ALARM WORK SHALL BE | | PERFORMED UNDER SEPARATE PERMITS AND SHOP DRAWINGS. THE | | WORK IS TO BE PERFORMED BY QUALIFIED, PROPERLY LICENSED | | CONTRACTORS. | | | | 3. ANY IMPAIRMENTS TO THE FIRE/LIFE SAFETY SYSTEMS IN | | EXCESS OF 4 HOURS DURATION SHALL REQUIRE A FIRE WATCH | | TO BE IMPLEMENTED. | | |
|