Plan Review Notes
Plan Review Notes For Permit 21121211
Permit Number 21121211
Review Stop P
Sequence Number 2
Notes
Date Text
2022-07-05 11:12:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121211 2300 VILLAGE BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. SECOND REQUEST: PLAN SHEET A-1/CODE ANALYSIS: THE
 2020 FLORIDA BUILDING CODES, SEVENTH EDITION INCLUSIVE
 OF FLORIDA BUILDING CODE ENERGY CONSERVATION, FLORIDA
 ACCESSIBILITY CODE 2020, FLORIDA EXISTING BUILDING CODE
 2020, FLORIDA PLUMBING CODE 2020 AND FLORIDA FUEL GAS
 CODE 2020 7TH EDITION ARE THE APPLICABLE CODES. PER WPB
 FBC 107.2.1, PLEASE CORRECT.
 TO BE CLEAR, PROVIDE THE CURRENT EDITION DATE OF 2020
 FOR THE APPLICABLE CODES
 NEW COMMENT: WPB AMENDMENTS TO THE FLORIDA BUILDING
 CODE (2017), CHAPTER 1, ADMINISTRATION SHALL BE LISTED,
 NOT THE PALM BEACH COUNTY AMENDMENTS
  
 2. COMPLIED
  
 3. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE CONFIRM
 THAT THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING IS WITHIN 50 FEET OF THE SOURCE OF HOT WATER AS
 DEFINED IN FBC PL 607.2.
 TO BE CLEAR, AN ACCEPTABLE SOURCE OF HOT WATER FOR HOT
 OR TEMPERED WATER IS A RECIRCULATING HOT WATER SYSTEM
 OR A HEAT TRACED PIPING SYSTEM, (OR A WATER HEATER) NOT
 A MIXING VALVE. FBC PL 607.2.
 PER WPB FBC 107.2.1, PLEASE CLARIFY ON THE PLANS.
  
 LINE ITEMS 4 THROUGH 14. COMPLIED
  
 NEW COMMENTS:
  
 1. NEW COMMENT: SPECIFIED LEONARD 6020-LF SERVICING
 EYEWASH DOES NOT COMPLY WITH ASSE 1071 AS REQUIRED BY
 FBC PL 411.3. PER WPB FBC 107.2.1, PROVIDE COMPLIANT
 TMV.
  
 2. NEW COMMENT: PER FBC PL 608.1, PROVIDE RPZ IN HOT
 WATER LINE TO TMV SERVICING THE P-1 DIALYSIS BOXES.
  
 3. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION AND DETAIL FOR RPZ, INCLUDING DISCHARGE
 WITH AIR GAP TO FLOOR SINK.
  
 4. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION AND DETAIL FOR PRV WITH STRAINER TO
 REGULATE PRESSURE AT THE RPZ TO 25PSI MAX AS NOTED ON
 THE PLANS. COMPLY WITH FBC PL 604.8, 604.8.1 AND
 604.8.2.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  