Date |
Text |
2022-07-05 11:12:51 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21121211 2300 VILLAGE BLVD |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1. SECOND REQUEST: PLAN SHEET A-1/CODE ANALYSIS: THE |
| 2020 FLORIDA BUILDING CODES, SEVENTH EDITION INCLUSIVE |
| OF FLORIDA BUILDING CODE ENERGY CONSERVATION, FLORIDA |
| ACCESSIBILITY CODE 2020, FLORIDA EXISTING BUILDING CODE |
| 2020, FLORIDA PLUMBING CODE 2020 AND FLORIDA FUEL GAS |
| CODE 2020 7TH EDITION ARE THE APPLICABLE CODES. PER WPB |
| FBC 107.2.1, PLEASE CORRECT. |
| TO BE CLEAR, PROVIDE THE CURRENT EDITION DATE OF 2020 |
| FOR THE APPLICABLE CODES |
| NEW COMMENT: WPB AMENDMENTS TO THE FLORIDA BUILDING |
| CODE (2017), CHAPTER 1, ADMINISTRATION SHALL BE LISTED, |
| NOT THE PALM BEACH COUNTY AMENDMENTS |
| |
| 2. COMPLIED |
| |
| 3. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE CONFIRM |
| THAT THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER |
| PIPING IS WITHIN 50 FEET OF THE SOURCE OF HOT WATER AS |
| DEFINED IN FBC PL 607.2. |
| TO BE CLEAR, AN ACCEPTABLE SOURCE OF HOT WATER FOR HOT |
| OR TEMPERED WATER IS A RECIRCULATING HOT WATER SYSTEM |
| OR A HEAT TRACED PIPING SYSTEM, (OR A WATER HEATER) NOT |
| A MIXING VALVE. FBC PL 607.2. |
| PER WPB FBC 107.2.1, PLEASE CLARIFY ON THE PLANS. |
| |
| LINE ITEMS 4 THROUGH 14. COMPLIED |
| |
| NEW COMMENTS: |
| |
| 1. NEW COMMENT: SPECIFIED LEONARD 6020-LF SERVICING |
| EYEWASH DOES NOT COMPLY WITH ASSE 1071 AS REQUIRED BY |
| FBC PL 411.3. PER WPB FBC 107.2.1, PROVIDE COMPLIANT |
| TMV. |
| |
| 2. NEW COMMENT: PER FBC PL 608.1, PROVIDE RPZ IN HOT |
| WATER LINE TO TMV SERVICING THE P-1 DIALYSIS BOXES. |
| |
| 3. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE |
| SPECIFICATION AND DETAIL FOR RPZ, INCLUDING DISCHARGE |
| WITH AIR GAP TO FLOOR SINK. |
| |
| 4. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE |
| SPECIFICATION AND DETAIL FOR PRV WITH STRAINER TO |
| REGULATE PRESSURE AT THE RPZ TO 25PSI MAX AS NOTED ON |
| THE PLANS. COMPLY WITH FBC PL 604.8, 604.8.1 AND |
| 604.8.2. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |