2022-02-03 16:16:06 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21121211 2300 VILLAGE BLVD |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1. PLAN SHEET A-1/CODE ANALYSIS: THE 2020 FLORIDA |
| BUILDING CODES, SEVENTH EDITION INCLUSIVE OF FLORIDA |
| BUILDING CODE ENERGY CONSERVATION, FLORIDA |
| ACCESSIBILITY CODE 2020, FLORIDA EXISTING BUILDING CODE |
| 2020, FLORIDA PLUMBING CODE 2020 AND FLORIDA FUEL GAS |
| CODE 2020 7TH EDITION ARE THE APPLICABLE CODES. PER WPB |
| FBC 107.2.1, PLEASE CORRECT. |
| |
| 2. PER WPB FBC 107.2.1, PROVIDE DEMO PLAN SHOWING THE |
| CURRENT CONDITIONS AND DIRECTION FOR |
| REMOVAL/REMEDIATION OF EXISTING PLUMBING FIXTURES, |
| EQUIPMENT AND PIPING. |
| |
| 3. PER WPB FBC 107.2.1, PLEASE CONFIRM THAT THE |
| DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING IS |
| WITHIN 50 FEET OF THE SOURCE OF HOT WATER AS DEFINED IN |
| FBC PL 607.2. |
| |
| 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION SHEETS/INSTALLATION MANUAL FOR PLUMBING |
| FIXTURE ITEM P-4/SHAMPOO SINK; SPECIFY AND PROVIDE |
| MANUFACTURER'S SPECIFICATION SHEETS/INSTALLATION MANUAL |
| FOR THE HAIR TRAP/INTERCEPTOR. INDICATE THE INTERCEPTOR |
| ON THE PIPING PLANS AND PROVIDE A DETAIL. |
| |
| 5. PER WPB FBC 107.2.1, ADD FIXTURE TAG (I.E. P-1, P-2, |
| ETC.) TO FIXTURES ON RISER DIAGRAMS AND RECONCILE WITH |
| PLAN VIEW. |
| |
| 6. FIXTURE P-3 SINK COMES WITH EYEWASH INTEGRAL WITH |
| THE FAUCET. WATER RISER DIAGRAM SHOWS EYEWASH AS A |
| SEPARATE ENTITY WITH A TWO SEPARATE THERMAL MIXING |
| VALVES, ONE FOR THE SINK FAUCET AND ONE FOR THE |
| EYEWASH. PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| |
| 7. PLAN SHEET P-1 AND P-2 SHOW THE P-5 EYEWASH AT |
| OPPOSITE P-2 SINKS. PER WPB FBC 107.2.1, PLEASE CLARIFY |
| AND RECONCILE. |
| |
| 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION SHEETS/INSTALLATION MANUAL FOR PLUMBING |
| FIXTURE ITEM P-1/DIALYSIS BOX. |
| |
| 9. PLAN SHEET P-1/PLUMBING GENERAL NOTE 8 REQUIRES PVC |
| FOR SANITARY PIPING IF APPROVED BY LOCAL CODE, |
| OTHERWISE USE CAST IRON. PRIOR TO INSPECTION, A PLAN |
| REVISION REFLECTING THE ACTUAL MATERIAL SHALL BE |
| SUBMITTED TO THE BUILDING DEPARTMENT, APPROVED AND ON |
| SITE. WPB FBC 107.2.1. |
| |
| 10. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| STATING THE SAME. |
| |
| 11. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| WALL/FLOOR DETAILS FOR PLUMBING PIPE PENETRATIONS |
| COMPLYING WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| |
| 12. PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PIPE |
| HANGER DETAIL STATING, "HORIZONTAL PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| 13. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR |
| SIZING OF SANITARY AND WATER DISTRIBUTION. |
| |
| 14. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DIALYSIS |
| EQUIPMENT. THIS MAY BE DONE AS A DEFERRED SUBMITTAL IN |
| ACCORDANCE WITH WPB FBC 107.3.4.2. THE ITEMS SHALL BE |
| LISTED ON THE PLANS AS DEFERRED SUBMITTALS TO BE |
| SUBMITTED TO THE BUILDING OFFICIAL, APPROVED AND ON |
| SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| RISK. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |