Plan Review Notes
Plan Review Notes For Permit 21121211
Permit Number 21121211
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-03 16:16:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121211 2300 VILLAGE BLVD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PLAN SHEET A-1/CODE ANALYSIS: THE 2020 FLORIDA
 BUILDING CODES, SEVENTH EDITION INCLUSIVE OF FLORIDA
 BUILDING CODE ENERGY CONSERVATION, FLORIDA
 ACCESSIBILITY CODE 2020, FLORIDA EXISTING BUILDING CODE
 2020, FLORIDA PLUMBING CODE 2020 AND FLORIDA FUEL GAS
 CODE 2020 7TH EDITION ARE THE APPLICABLE CODES. PER WPB
 FBC 107.2.1, PLEASE CORRECT.
  
 2. PER WPB FBC 107.2.1, PROVIDE DEMO PLAN SHOWING THE
 CURRENT CONDITIONS AND DIRECTION FOR
 REMOVAL/REMEDIATION OF EXISTING PLUMBING FIXTURES,
 EQUIPMENT AND PIPING.
  
 3. PER WPB FBC 107.2.1, PLEASE CONFIRM THAT THE
 DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING IS
 WITHIN 50 FEET OF THE SOURCE OF HOT WATER AS DEFINED IN
 FBC PL 607.2.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR PLUMBING
 FIXTURE ITEM P-4/SHAMPOO SINK; SPECIFY AND PROVIDE
 MANUFACTURER'S SPECIFICATION SHEETS/INSTALLATION MANUAL
 FOR THE HAIR TRAP/INTERCEPTOR. INDICATE THE INTERCEPTOR
 ON THE PIPING PLANS AND PROVIDE A DETAIL.
  
 5. PER WPB FBC 107.2.1, ADD FIXTURE TAG (I.E. P-1, P-2,
 ETC.) TO FIXTURES ON RISER DIAGRAMS AND RECONCILE WITH
 PLAN VIEW.
  
 6. FIXTURE P-3 SINK COMES WITH EYEWASH INTEGRAL WITH
 THE FAUCET. WATER RISER DIAGRAM SHOWS EYEWASH AS A
 SEPARATE ENTITY WITH A TWO SEPARATE THERMAL MIXING
 VALVES, ONE FOR THE SINK FAUCET AND ONE FOR THE
 EYEWASH. PER WPB FBC 107.2.1, PLEASE CLARIFY.
  
 7. PLAN SHEET P-1 AND P-2 SHOW THE P-5 EYEWASH AT
 OPPOSITE P-2 SINKS. PER WPB FBC 107.2.1, PLEASE CLARIFY
 AND RECONCILE.
  
 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR PLUMBING
 FIXTURE ITEM P-1/DIALYSIS BOX.
  
 9. PLAN SHEET P-1/PLUMBING GENERAL NOTE 8 REQUIRES PVC
 FOR SANITARY PIPING IF APPROVED BY LOCAL CODE,
 OTHERWISE USE CAST IRON. PRIOR TO INSPECTION, A PLAN
 REVISION REFLECTING THE ACTUAL MATERIAL SHALL BE
 SUBMITTED TO THE BUILDING DEPARTMENT, APPROVED AND ON
 SITE. WPB FBC 107.2.1.
  
 10. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 11. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PIPE PENETRATIONS
 COMPLYING WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 12. PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PIPE
 HANGER DETAIL STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 13. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR
 SIZING OF SANITARY AND WATER DISTRIBUTION.
  
 14. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DIALYSIS
 EQUIPMENT. THIS MAY BE DONE AS A DEFERRED SUBMITTAL IN
 ACCORDANCE WITH WPB FBC 107.3.4.2. THE ITEMS SHALL BE
 LISTED ON THE PLANS AS DEFERRED SUBMITTALS TO BE
 SUBMITTED TO THE BUILDING OFFICIAL, APPROVED AND ON
 SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]