Date |
Text |
2022-03-09 15:17:45 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21121211 |
| ADD: 2300 VILLAGE BLVD. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. MARCH 09TH/2022 |
| ACTION: DENIED |
| |
| 1) 1S FLOOR PLAN CODE ANALYSIS STATES THE APPLICABLE |
| CODES ARE THE 2017 FAMILY OF FBC. UPDATE PLAN, THE |
| 2020FBC- FAMILY OF CODES WAS ADOPTED STATEWIDE DEC. 31/ |
| 2020. |
| |
| |
| 2)SHEET A-4: |
| |
| 2A) BEAUTY/ BARBER SHOP. PLEASE SHOW COMPLIANCE WITH |
| THE 2020 FBC-BUILDING CODE SECTION 450.3.4.4 A BARBER/ |
| BEAUTY ROOM, THE AREA OF THE ROOM SHALL BE A MINIMUM OF |
| 120 SQUARE FEET WITH THE LEAST DIMENSION OF 10 FEET. |
| THE NINE FEET SIX INCHES IS 9 FEET 2 INCHES INSIDE OF |
| THE ROOM FINISH TO FINISH AND LESS THAN 120 SQUARE |
| FEET, 120 SQUARE FEET IS MINIMUM ROOM SIZE. |
| |
| 2B) PLEASE PROVIDE THE WIDTH OF DOOR #1,2, 3 & 4. 2020 |
| FBC-B 1010.1.1. SIZE OF DOORS. CLEAR WIDTH. DOOR |
| OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES |
| MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS |
| SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE |
| STOP, WITH THE DOOR OPEN AT 90 DEGREES. |
| |
| 3) GUIDELINES HEALTH CARE FACILITIES (3.10 RENAL |
| DIALYSIS UNIT (ACUTE & CHRONIC): |
| 3A) 2.2.2.1 SPACE REQUIREMENTS |
| (1) AREA. INDIVIDUAL PATIENT TREATMENT AREAS SHALL |
| CONTAIN AT LEAST 80 SQ. FT. EXCLUSIVE OF GENERAL |
| CIRCULATION SPACE WITHIN WARD. |
| (2) CLEARANCE. THERE SHALL BE AT LEAST A 4-FOOT SPACE |
| BETWEEN BEDS AND OR LOUNGE CHAIRS. |
| |
| 3B) PRIVACY. 2.2.2.2. THE OPEN UNIT SHALL BE DESIGNED |
| TO PROVIDE PRIVACY FOR EACH PATIENT. |
| |
| 3C) 2.2.4.2. HAND WASHING STATION. THERE SHALL BE AT |
| LEAST ONE HAND WASHING STATION SERVING NO MORE THAN |
| FOUR STATIONS. THE HAND WASHING STATIONS SHALL BE |
| UNIFORMLY DISTRIBUTED TO PROVIDE EQUAL ACCESS FROM EACH |
| PATIENT STATION. |
| |
| 3D) 3.2.2.1 CLEAN ROOM STORAGE. LOCATION OF THE CLEAN |
| LINEN STORAGE AREA WITHIN THE CLEAN WORKROOM, A |
| SEPARATE CLOSET. OR AN APPROVED DISTRIBUTION SYSTEM |
| SHALL BE PERMITTED. |
| |
| 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |