2022-02-14 13:41:12 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL16709-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R9 SELECTED SYSTEM NO W-1; EXPOSURE |
| (C); ENCLOSURE (OPEN); ROOF HEIGHT (H < 15); ULTIMATE |
| WIND SPEED IS 170 (MPH). THE CORRECT ENCLOSURE FOR THE |
| LISTED ADDRESS IS ENCLOSED. ZONE 3 IS MARKED ?N/A? |
| WHICH INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1 |
| PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED. |
| PLEASE SELECT THE CORRECT OPTIONS; CONSIDER USING |
| FL16709-R9 SYSTEM NO. W-3; EXPOSURE C; CLOSED; ZONE 1 |
| PRIME, ZONE 1 & ZONE 2 #1 (AS-LISTED), ZONE 3 #3; H < |
| 15; 170 (MPH). |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |