Plan Review Notes
Plan Review Notes For Permit 21121189
Permit Number 21121189
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-14 13:41:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL16709-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 SELECTED SYSTEM NO W-1; EXPOSURE
 (C); ENCLOSURE (OPEN); ROOF HEIGHT (H < 15); ULTIMATE
 WIND SPEED IS 170 (MPH). THE CORRECT ENCLOSURE FOR THE
 LISTED ADDRESS IS ENCLOSED. ZONE 3 IS MARKED ?N/A?
 WHICH INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1
 PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED.
 PLEASE SELECT THE CORRECT OPTIONS; CONSIDER USING
 FL16709-R9 SYSTEM NO. W-3; EXPOSURE C; CLOSED; ZONE 1
 PRIME, ZONE 1 & ZONE 2 #1 (AS-LISTED), ZONE 3 #3; H <
 15; 170 (MPH).
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  