2022-05-16 16:03:17 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21121068 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| ORIGINAL COMMENT: |
| 1-SURVEY/DRAINAGE PLAN SUBMITTED: |
| A)SITE PLAN & BOUNDARY SURVEY SUBMITTED SHOW "PROPOSED |
| RETAINING WALL" ON THE EAST SIDE. CLEARLY IDENTIFY |
| LOCATION OF PROPOSED RETAINING WALL. AND, PROVIDE |
| COMPLETE DETAILS/SPECIFICATIONS FOR THE RETAINING WALL |
| CONSTRUCTION. SEC. 107.2.5 CITY AMENDMENTS. R401.3 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| SURVEY/DRAINAGE PLAN WAS REVISED. RETAINING WALL WAS |
| DELETED. REVISED SURVEY DOESN'T SHOW HOW THE WATER IS |
| RETAINED WITHING THE LOT ON THE EAST SIDE. NOTE: |
| DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED GRADE |
| ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM ADJACENT |
| PROPERTIES. AND, THERE ARE NOT DETAILS LIKE SWALES |
| SHOWING HOW THE WATER IS RUNNING TOWARD THE FRONT AND |
| REAR OF PROPERTY. |
| |
| B)OK. NOT RETAINING WALL. |
| |
| 2- OK. |
| |
| ORIGINAL COMMENT: |
| 3- WIND RESISTANCE OF EXTERIOR SOFFITS: |
| TYPICAL WALL SECTION ON SHEET 3-4 ONLY SPECIFIES |
| "METHAL LATH AND STUCCO SOFFIT W/ 7"X24" SCREENED VENTS |
| @ 8'-0" O.C.". THERE ARE NO SPECIFICATIONS FOR |
| SHEATHING TO SUPPORT THE METHAL LATH. ENGINEER OF |
| RECORD TO PROVIDE CALCULATIONS SHOWING THAT THIS SOFFIT |
| SPECIFICATIONS WITHOUT SHEATHING ARE ADEQUATE TO RESIST |
| THE WIND LOADS AS REQUIRED BY SEC. R704 FBC-RESIDENTIAL |
| OR REVISE DETAIL PROVIDING COMPLETE SHEATHING |
| SPECIFICATIONS (MATERIAL, THICKNESS AND FASTENING). |
| SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| CLARIFY/REVISE SOFFIT SPECIFICATIONS. SPECIFICATIONS |
| CALL FOR 3/8" FLAT RIB LATH. 3/8" RIB LATH ARE NOT FLAT |
| RIB. 3/8" RIB LATH ARE ALSO CALLED HIGH RIB OR EXPANDED |
| METHAL LATH NOT FLAT RIB. ALSO, 6D NAILS DON'T PROVIDE |
| 1-3/4" EMBEDMENT. NEED TO USE ALT LEAST 2-1/2' LONG |
| NAILS (GALVANIZED ROOFING NAILS OR GALVANIZED COMMON |
| NAILS). |
| |
| 4- OK. |
| 5- OK. |
| 6- OK. |
| 7- OK. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |