Plan Review Notes
Plan Review Notes For Permit 21121041
Permit Number 21121041
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-06 10:23:46JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R8 HAS BEEN REVISED TO FL16709-R9.
 PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS.
 INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. NOTE: IF USING INSULATION AS
 PER CONTRACT, SELECT SYSTEM THAT INCLUDES INSULATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  