Date |
Text |
2023-05-02 14:24:15 | BUILDING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| BU1635 BN4338 |
| ASFPM CFM US-21-11935 |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| |
| 1. CORRECTED. |
| |
| 2. THE PREVIOUSLY APPROVED ELEVATION CERTIFICATE SHOWS |
| THE GARAGE IS 693 SF. PLAN PAGE A-0.1 SHOWS THE GARAGE |
| IS 693 SF. PLAN PAGE A-1.1 SHOWS THE GARAGE IS 685 SF. |
| PLEASE CORRECT PG A-1.1. (NOT CORRECTED) |
| |
| 3. CORRECTED. |
| |
| NEW COMMENTS: |
| |
| 4. FLOOD OPENINGS ON FLOOR PLAN A-1.1 ARE IDENTIFIED BY |
| A LEGEND KEY OF "O" . NO SCHEDULE OF OPENINGS IS |
| PROVIDED. THIS IS NOT AN ACCEPTABLE WAY TO IDENTIFY THE |
| FLOOD VENTS. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 5. IDENTIFY THE FLOOD OPENINGS (SMART VENTS) ON FLOOR |
| PLAN A-1.1 WITH THE PRODUCT APPROVAL NUMBER, MODEL |
| NUMBER AND COVERAGE AREA NEXT TO EACH |
| OPENING.FL5822-R8, MODEL 1540-520, COVERAGE 200SF. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |