Plan Review Notes
Plan Review Notes For Permit 21121009
Permit Number 21121009
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-04 12:43:51BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REFERENCE PLAN PAGES C-1 AND A.01 FOR THE FOLLWING
 COMMENT:
 THE GARAGE FLOOR ELEVATION IS AT 6.0' NAVD (CENTER OF
 ROOM). THERE IS A REQUIRED 1/4" SLOPE. ADDING THE
 STANDARD 1 1/2" RECESS FOR THE OHD, THE GARAGE FLOOR
 WILL BE AT APPROX. 3 1/2" TO 4' BELOW THE DRIVEWAY
 GRADE OF 6.0'NAVD.
  
 2. THE PREVIOUSLY APPROVED ELEVATION CERTIFICATE SHOWS
 THE GARAGE IS 693 SF. PLAN PAGE A-0.1 SHOWS THE GARAGE
 IS 693 SF. PLAN PAGE A-1.1 SHOWS THE GARAGE IS 685 SF.
 PLEASE CORRECT PG A-1.1.
  
 3. PROVIDE THE FLORIDA PRODUCT APPROVALS AND THE ICC-ES
 REPORT FOR THE PROPOSED SMART VENTS (MODEL 1540-51).
 APPROVED UNDER THE 2020 FBC,
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  