2021-12-22 15:52:28 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21120912 |
| 12/22/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) P1: THE PLUMBING PLAN, AND THE PLUMBING AND |
| ELECTRICAL SPECS FOR THE DRINKING FOUNTAIN APPEAR TO |
| HAVE BEEN COPIED AND PASTED ONTO THE LANDSCAPE PLANS. |
| PLEASE NOTE THAT LANDSCAPE ARCHITECTS CANNOT DESIGN |
| PLUMBING AND ELECTRICAL PLANS- FL. STATUTE- 481.303. |
| PLEASE PROVIDE SEPARATE PLUMBING AND ELECTRICAL PLANS- |
| SECTION 107.2.1 WPB. |
| |
| 2) P1: THE DRINKING FOUNTAIN SHALL DRAIN INTO THE |
| SANITARY SEWER SYSTEM IN COMPLIANCE WITH SEC. 301.3 FBC |
| P. PLEASE PROVIDE A SANITARY DRAINAGE LAYOUT PLAN AND |
| ISOMETRIC DRAWING SHOWING THE BRANCH DRAIN LINE |
| CONNECTION TO THE MAIN- SEC. 107.3.5.1.3 WPB. |
| |
| 3) P1: PLEASE PROVIDE WATER SUPPLY LAYOUT AND ISOMETRIC |
| DRAWING SHOWING THE DRINKING FOUNTAIN BRANCH LINE |
| CONNECTION TO THE MAIN SERVICE LINE- SEC. 107.2.1 WPB. |
| |
| 4) P1: THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE IN |
| COMPLIANCE WITH SEC. 211.1 FBC ACC. |
| |
| 5) P1: NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE |
| PROVIDED- ONE COMPLYING WITH 602.1 AND ONE COMPLYING |
| WITH 602.7- (HI-LO). REFER TO SECTIONS 306, 307, AND |
| 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION |
| 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE |
| FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| PROTRUSION LIMITS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |