2022-01-13 14:20:24 | SIGNATURE REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| RE: ELECTRICAL RISER DIAGRAHM |
| |
| 1. THE ELECTRICAL CONTRACTOR OR DESIGNER OF RECORD |
| SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN |
| SHEETS UNDER THEIR AUTHORITY. |
| 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, SECTION 107.2.1. |
| |
| 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL |
| WITH SIGNATURE OF CONTRACTOR OR DESIGNER, AS |
| APPLICABLE; USE THE REQUIRED NAMING CONVENTION FOR EACH |
| DOCUMENT OR DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH |
| CONTRACTORS/O/B SIGNATURE TO: |
| |
| BUILDING DIVISION, FIRST FLOOR |
| CITY OF WEST PALM BEACH |
| 401 CLEMATIS ST |
| WEST PALM BEACH, FL 33401 |
| |
| FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| 481, F.S. & 61G1. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |