2021-12-22 15:52:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF FIRE LINE UNDERGROUND |
| WORK. |
| |
| FIRE LINE UNDERGROUND WORK, INCLUDING THE DDCV, SHALL |
| BE SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| THIS PERMIT WILL NOT BE APPROVED FOR UNDERGROUND WORK. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGMENT THAT A SPEARATE FIRE LINE UNDEGROUND |
| PERMIT WILL BE SUBMITTED. |
| |
| |
| 1A) A SEPARATE WATER METER & TAP IS REQUIRED BY THE |
| CITY'S UTILITY DEPARTMENT FOR FIRE SPRINKLER SYSTEMS, |
| INCLUDING 13R. |
| |
| PLEASE CONTACT THAT DEPARTMENT FOR THEIR REQUIREMENTS |
| FOR THE SEPARATE PERMIT(S). |
| |
| |
| 2) IT APPEARS THAT THIS OCCUPANCY MAY BE A NEW |
| RESIDENTIAL BOARD & CARE FACILITY AS SUCH SHALL COMPLY |
| WITH NFPA 101, CH 32. |
| |
| PER THAT CHAPTER : |
| |
| 32.2.3.5.3.1 IN BUILDINGS FOUR OR FEWER STORIES IN |
| HEIGHT AND NOT EXCEEDING |
| 60 FT (18.3 M) IN HEIGHT ABOVE GRADE PLANE, SYSTEMS IN |
| ACCORDANCE |
| WITH NFPA 13R SHALL BE PERMITTED. ALL HABITABLE AREAS, |
| CLOSETS, ROOFED |
| PORCHES, ROOFED DECKS, AND ROOFED BALCONIES SHALL BE |
| SPRINKLERED |
| |
| THERE APPEARS TO BE CLOSETS WITHOUT FS PROTECTION AS |
| WELL AS ROOFED BALCONIES. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC A |
| DETAILED NARRATIVE AND FIRE CODE REFERENCES. |
| |
| |
| |
| 3) IT APPEARS THAT THIS BUILDING MAY HAVE AN ATTIC OR A |
| ROOM ON THE ROOF. |
| |
| |
| PER THAT CHAPTER : |
| |
| 32.2.3.5.7 ATTICS SHALL BE PROTECTED IN ACCORDANCE WITH |
| 32.2.3.5.7.1 OR |
| 32.2.3.5.7.2. |
| 32.2.3.5.7.1 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| REQUIRED BY |
| 32.2.3.5, ATTICS USED FOR LIVING PURPOSES, STORAGE, OR |
| FUEL-FIRED EQUIPMENT |
| SHALL BE PROTECTED WITH AUTOMATIC SPRINKLERS THAT ARE |
| PART OF THE REQUIRED, |
| APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| 9.7.1.1. |
| 32.2.3.5.7.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| REQUIRED BY |
| 32.2.3.5, ATTICS NOT USED FOR LIVING PURPOSES, STORAGE, |
| OR FUEL-FIRED EQUIPMENT |
| SHALL MEET ONE OF THE FOLLOWING CRITERIA: |
| (1) ATTICS SHALL BE PROTECTED THROUGHOUT BY A HEAT |
| DETECTION SYSTEM |
| ARRANGED TO ACTIVATE THE BUILDING FIRE ALARM SYSTEM IN |
| ACCORDANCE |
| WITH SECTION 9.6. |
| (2) ATTICS SHALL BE PROTECTED WITH AUTOMATIC SPRINKLERS |
| THAT ARE PART OF |
| THE REQUIRED, APPROVED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH 9.7.1.1. |
| (3) ATTICS SHALL BE OF NONCOMBUSTIBLE OR |
| LIMITED-COMBUSTIBLE |
| CONSTRUCTION. |
| (4) ATTICS SHALL BE CONSTRUCTED OF |
| FIRE-RETARDANT-TREATED WOOD IN ACCORDANCE |
| WITH NFPA 703. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC A |
| DETAILED NARRATIVE AND FIRE CODE REFERENCES. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |