Plan Review Notes
Plan Review Notes For Permit 21120760
Permit Number 21120760
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-20 10:00:48JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 19-0311.04 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(24).
 SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS A
 CATEGORY C AREA.
 2. FBC B 107.2.1 SUBMITTED FORM 400 IS A PALM BEACH
 COUNTY BUILDING DEPARTMENT DOCUMENT AND IS NOT APPROVED
 FOR USE AS A SUBSTITUTE FOR SIGNED AND SEALED ENHANCED
 NAILING CALCULATIONS BY THE CITY OF WEST PALM BEACH
 BUILDING DEPARTMENT THE AUTHORITY OF JURISDICTION.
 GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. SUBMIT FASTENER DENSITY CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT.
 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF COATING SYSTEM TO
 BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 4. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT
 COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL
 AND CHAPTER 11 OF THE 2020 FBC-PLUMBING
 5. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR
 THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL
 HEIGHT(S).
 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS
 MUST SHOW POSITIVE DRAINAGE.
 7. FBC EB 706.8.1 PROVIDE A DETAILED COST ESTIMATE OF
 THE EVALUATION AND INSTALLATION OF CONNECTIONS AT THE
 GABLE ENDS OR ALL CORNERS THAT WILL EXCEED 15% OF THE
 COST OF THE ROOF REPLACEMENT WHEN COMPLETED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  
  