2022-04-20 10:00:48 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. SUBMITTED MIAMI-DADE COUNTY NOA 19-0311.04 COVERS |
| MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(24). |
| SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED |
| CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS A |
| CATEGORY C AREA. |
| 2. FBC B 107.2.1 SUBMITTED FORM 400 IS A PALM BEACH |
| COUNTY BUILDING DEPARTMENT DOCUMENT AND IS NOT APPROVED |
| FOR USE AS A SUBSTITUTE FOR SIGNED AND SEALED ENHANCED |
| NAILING CALCULATIONS BY THE CITY OF WEST PALM BEACH |
| BUILDING DEPARTMENT THE AUTHORITY OF JURISDICTION. |
| GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN |
| THIS NOA. SUBMIT FASTENER DENSITY CALCULATIONS |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR |
| REGISTERED ROOF CONSULTANT. |
| 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ROOF COATING SYSTEM TO |
| BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| 4. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT |
| COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL |
| AND CHAPTER 11 OF THE 2020 FBC-PLUMBING |
| 5. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR |
| THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL |
| HEIGHT(S). |
| 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW |
| ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF |
| SLOPE(S), MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS |
| MUST SHOW POSITIVE DRAINAGE. |
| 7. FBC EB 706.8.1 PROVIDE A DETAILED COST ESTIMATE OF |
| THE EVALUATION AND INSTALLATION OF CONNECTIONS AT THE |
| GABLE ENDS OR ALL CORNERS THAT WILL EXCEED 15% OF THE |
| COST OF THE ROOF REPLACEMENT WHEN COMPLETED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |
| |