2022-01-05 11:08:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21120658
 ADD: 1801 S. FLAGLER DR. # 503
 CONT: HAROLD M. GORDON & SONS
 TEL: 561-832-3211
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 05TH/2022
 ACTION: DENIED
  
 1) THE FLOOR PLAN DOES NOT INDICATE THE AUTHOR OF THE
 PLAN. CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
  
 2) THE ENGINEERING SHEET FROM W. W. SCHAEFER INDICATES
 ALL IN ZONE 5 EXCEPT FOR 3 MULLED SINGLE HUNG WINDOW
 UNITS IN ZONE 4. PLEASE REVIEW THE FLOOR PLAN THERE ARE
 3 BEDROOMS WITH 3 OPENINGS (6 MULLED WINDOWS) THAT ARE
 FURTHER BACK FROM THE CORNER WHERE ZONE 5 WOULD BE. THE
 WAY THE ENGINEER WORDED THESE WINDOWS WOULD ALSO BE IN
 ZONE 5? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) THE ENGINEERING SHEET FROM W. W. SCHAEFER INDICATES
 THE REPLACEMENT OF AN OUTSWING DOOR. NO PRODUCT
 APPROVAL WAS SUBMITTED FOR THIS OPENING. COMPONENTS &
 CLADDING. PLEASE SUBMIT THE COMPONENTS AND CLADDING
 PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:(31)(A) EXTERIOR DOORS,
  
 4) SUBMITTED MIAMI-DADE SLIDING GLASS DOORS NOA
 20-0814.03 PLEASE IDENTIFY IN THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 5) SUBMITTED MIAMI-DADE NOA SINGLE HUNG WINDOWS
 20-0722.20 03 PLEASE IDENTIFY IN THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  