2021-12-17 11:29:13 | 12/17/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT |
| SYSTEM. A COMPLETE EVALUATION OF ALL GAS SYSTEMS AND |
| EQUIPMENT WILL BE DONE AT THIS STAGE, AND IF NOT TO |
| CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT |
| THE OWNER?S EXPENSE. PLEASE INCLUDE THE CURRENT AND NEW |
| GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE |
| OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| SOME OF THE ITEMS BELOW MAY BE NEEDED FOR REVIEW! |
| |
| 2. WOULD YOU PLEASE SHOW THE ISOMETRIC DRAWING THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. |
| SECS. G2413.4.1, G2413.4.2. |
| |
| 3. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER |
| OF THE CORRUGATED STAINLESS STEEL TUBING PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. THE TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN, AND |
| THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| SEC. G2421.1. |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR (CLOTHES |
| DRYERS AND RANGE) PER THE 2020 FBC RES. SEC. G2407.1 |
| AND G2439.4. IF USING LOUVERS, HOW THE LOCATION THAT IS |
| BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS |
| CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS FIRE |
| RATED AS THE FIRE RATING OF THE WALL MUST BE MAINTAINED |
| PER THE WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 7. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. |
| SEC G2421.2. |
| |
| 8. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON |
| GAS ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC |
| RES. SEC. G2420.5. |
| |
| 9. DRIP LEG IS MISSING ON TANKLESS PER THE 2020 FBC |
| RES. SEC. G2419.2. |
| |
| 10. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 11. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| 403.5.3. WOULD YOU PLEASE NOTE ON PLANS? |
| |
| 12. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM |
| THE STRUCTURE PER THE 2020 FBC SEC. R318.5. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| REQUEST. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |