Plan Review Notes
Plan Review Notes For Permit 21120578
Permit Number 21120578
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-05 16:10:15FAILED
  
 1) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE
 PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION
 OFFICE APPROVAL OF THIS LOCATION.
  
 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR IS TO MATCH THE COLOR OF THE DECORATIVE
 CONCRETE LIGHT POLE ADJACENT TO THE PROPOSED POLE
 LOCATION.
  
 3) THE PLANS SHOW A GAS LINE AND UNDERGROUND ELECTRIC
 WITHIN 2 FEET OF THE POLE CAISSON AND THE BORE PIT FOR
 THE UNDERGROUND ELECTRIC. IN ORDER TO VERIFY THAT THE
 INSTALLATION WILL NOT INTERFERE WITH THE EXISTING
 FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO
 OBJECTION FROM FPU REGARDING THE INSTALLATION.
  
 4) PROVIDE CROSS SECTIONS OF THE LOCATION OF THE
 UNDERGROUND ELECTRIC FOR THE FULL LENGTH OF THE
 INSTALLATION. THERE UNDERGROUND ELECTRIC MUST BE
 CLEARLY SHOWN AVOIDING THE STREET TREE ROOT SYSTEMS AND
 ANY INFRASTRUCTURE THAT IT CROSSES (EX: THE GAS LINE).
  
 5) THE SURVEY NEEDS TO SHOW THE SAME UNDERGROUND
 ELECTRIC PATH AS THE POWER ROUTE PLAN.
  