2021-12-23 09:31:32 | 1) BONDING JUMPER SHOWN ON SHEET 201 INCORRECTLY | | PARALLELS GROUNDED CONDUCTOR NEC 250.30 (A) | | 2) SHOW AVAILABLE FAULT CURRENT CALCULATION AND | | LABELING REQUIREMENTS. NEC 110.24 110.16 | | 3) VALUE APPEARS LOW. PLEASE PROVIDE A BREAKDOWN OF | | MATERIAL AND LABOR COSTS ASSOCIATED WITH THE PROJECT. | | W.P.B. AMENDMENTS 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|