Plan Review Notes
Plan Review Notes For Permit 21120572
Permit Number 21120572
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-03 17:37:53FAILED
  
 1) THERE ARE DIMENSIONS SHOWN ON THE ENGINEERING SITE
 PLAN THAT DO NOT MATCH THE SAME DIMENSIONS SHOWN ON THE
 SURVEY. ALL PLANS MUST SHOW THE SAME CONDITIONS.
  
 2) PLEASE MOVE THE POLE NORTH SO THAT IT IS IN LINE
 WITH THE ROYAL PALM TREE THAT IS LOCATED TO THE EAST OF
 THE PROPOSED POLE. PLEASE REVIEW THE STAFF MARK UP
 (GREEN LINE) ON SHEET C-2 IN PROJECTDOX.
  
 3) PROVIDE CROSS SECTIONS OF THE LOCATION OF THE
 UNDERGROUND ELECTRIC FOR THE FULL LENGTH OF THE
 INSTALLATION. THERE UNDERGROUND ELECTRIC DEPTH MUST BE
 CLEARLY SHOWN AVOIDING THE STREET TREE ROOT SYSTEMS AND
 ANY INFRASTRUCTURE THAT IT CROSSES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  