Plan Review Notes
Plan Review Notes For Permit 21120571
Permit Number 21120571
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-03-09 17:05:16INSUFFICIENT
  
 1) THE BORE PIT AND HANDHOLE NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE
 ALSO LOCATED WITHIN THE PARKWAY WHICH WILL NEED
 RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 2) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC
 WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH
 EXISTING UTILITIES AND TREE ROOTS.
  
 3) THE PLANS SHOW THE BORE PITS, HANDHOLE AND THE POLE
 INSTALL IN DIRECT OVERLAP OF ELECTRIC LINES AND WITHIN
 2 FEET OF A GAS LINE. IN ORDER TO VERIFY THAT THE
 INSTALLATION WILL NOT INTERFERE WITH THE EXISTING
 FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO
 OBJECTION FROM FPL AND FPU REGARDING THE INSTALLATION.
  
 4) THE EXCAVATION FOR THE HANDHOLE AT THE POWER POLE IS
 SHOWN CROSSING ONTO PRIVATE PROPERTY, WHICH IS NOT
 PERMITTED UNLESS THE SURVEY CLEARLY SHOWS A UTILITY
 EASEMENT AT THIS LOCATION.
  
 5) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  