Plan Review Notes For Permit 21120568 |
Permit Number |
21120568 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-03-17 12:33:00 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 21120568 | | 3/17/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE CORRECT POOL PLAN SHEET 3 SPECIFYING THE PUMP | | TO BE CS-150 0.85 HP. THE ENGINEER???S SIGNED AND | | SEALED TDH AND FLOW RATE CALCULATIONS ARE BASED ON A | | 1HP PUMP TO BE INSTALLED- SEC. R4501.6 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|