2021-12-15 12:03:12 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL1654-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE (CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). EVALUATION REPORT PAGES |
| 1-5 TO INCLUDE LIMITATIONS PAGE(S). |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL1654-R28 SYSTEM NO. W-209 DOES NOT MEET THE |
| MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| SYSTEM. |
| 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL20378.01-R3 IS NOT RATED FOR USE IN ZONE 3 |
| FOR STRUCTURES LOCATED IN EXPOSURE B, C OR D EXPOSURE |
| AREA HAVE EITHER FLAT ROOF, GABLE/HIP ROOF WITH MAX |
| SLOPE OF 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS |
| WIND SPEED 170 MPH. PROVIDE SIGNED AND SEALED |
| ENGINEERING FOR USE OR SELECT A SYSTEM THAT MEETS THE |
| ABOVE CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY |
| AREA. |
| 4. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R33 |
| SELECTED PRODUCT POLYSTIC IR-XE IS NOT APPROVED FOR USE |
| IN A METAL ROOF SYSTEM AS PER LIMITATIONS #5.6. SELECT |
| A PRODUCT THAT IS APPROVED FOR USE IN A METAL ROOF |
| SYSTEM. |
| 5. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF |
| DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW |
| SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD |
| OF PROVIDING POSITIVE DRAINAGE. |
| 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND INCLUDE MEAN ROOF HEIGHT(S). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |