2022-02-08 09:58:12 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| PERMIT- 21120514 |
| 2/8/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR THE |
| MAIN HOUSE AND ACCESSORY BUILDING- SEC. 105.1 & 107.2.1 |
| WPB. PLEASE REVIEW THE COMMENTS UNDER THE ADDRESSING |
| REVIEW. THE COMMENTS BELOW APPLY TO THE PLUMBING |
| INSTALLATIONS IN BOTH BUILDINGS. |
| |
| 2) TWO DWELLINGS ON THE SAME LOT WILL REQUIRE WATER |
| USERS TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE |
| POINT OF DELIVERY. A REDUCED PRESSURE ZONE (RPZ) |
| BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER METER |
| PER THE CITY OF WEST PALM UTILITIES DEPARTMENT AND |
| THEIR CROSS-CONNECTION CONTROL PROGRAM. |
| PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| 3) SHEET P.1: THE WASHING MACHINE VALVES IN BOTH THE |
| MAIN HOUSE AND THE ACCESSORY BUILDING SHALL BE |
| INSTALLED IN ACCESSIBLE LOCATIONS- SEC. P2903.9.3 FBC |
| RES. THE CURRENT PLANS SHOW NON-COMPLIANCE BECAUSE THE |
| VALVES ARE BEHIND THE STACKABLE W/D UNITS AND NOT |
| ACCESSIBLE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |