2022-03-25 09:41:14 | RESIDENTIAL (R3)ALTERATION BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21120514 |
| |
| NOTE: |
| GARAGE CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, |
| SEC. 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING |
| BUILDING. ALL NEW WORK SHALL COMPLY WITH THE MATERIALS |
| AND METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| |
| 1- THERE ARE TWO SEPARATE BUILDINGS IN THIS PROPERTY. A |
| SEPARATE PERMIT APPLICATION AND SUB-PERMITS ARE |
| REQUIRED FOR EACH BUILDING. PLEASE SUBMIT A SEPARATE |
| PERMIT APPLICATION AND SUB-PERMITS FOR THE ACCESSORY |
| STRUCTURE. SPECIFY VALUE FOR THE MAIN HOUSE AND VALUE |
| FOR THE ACCESSORY STRUCTURE. SAME PLANS CAN BE USED. |
| NOTE: SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE |
| INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS |
| RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| 2- NEED TO PROVIDE SURVEY SHOWING ACCESSORY BUILDING |
| SETBACKS. NEED TO VERIFY COMPLIANCE WITH THE FIRE |
| RESISTANT CONSTRUCTION REQUIREMENTS OF SEC. R302.1 AND |
| TABLE R302.1 FBC-RESIDENTIAL FOR NORTH AND WEST SIDE. |
| NOTE: OPENING IN WALLS MAY NOT ALLOWED IF LESS THAN |
| 3'-0" SETBACKS. |
| |
| 3- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE |
| SPACE. TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR |
| VAPOR BARRIER. ARCHITECT OF RECORD TO PROVIDE |
| SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS |
| REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL. |
| |
| 4- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS |
| AND CONNECTORS. SEC. R302.1 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR NEW WOOD MULLIONS AS SPECIFIED ON PLANS. SPECIFY |
| ALL FRAMING MEMBERS AND CONNECTORS. SEC. R302.1 |
| FBC-RESIDENTIAL. |
| |
| 6- REVISE WALL DISTANCE "A" SPECIFIED ON NOTES FOR |
| COMPONENTS AND CLADDING. MINIMUM WALL DISTANCE IS 4'-0" |
| NOT 3'-0". SEE FIGURE R302.2(7) FBC-RESIDENTIAL AND |
| REVISE AS REQUIRED. |
| |
| 7- DEFERRED SUBMITTALS: |
| (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| A)ALL WINDOW TYPES SHOWN ON PLANS. |
| B)ALL DOOR TYPES SHOWN ON PLANS. |
| C)ROOF TILE AND FLAT ROOF SHOWN ON PLANS. |
| |
| 8-ARCHITECT IS SPECIFYING R-30 FOAM INSULATION. PROVIDE |
| ICC EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION |
| TO VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| 9- SUBMIT COMPLETE INFORMATION FOR THE PERIMETER |
| CONCRETE WALL UNDER A SEPARATE PERMIT. SEC. 105.1 CITY |
| AMENDMENTS. |
| |
| 10- ENERGY CALCULATIONS SUBMITTED: THIS HOUSE IS A |
| CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE |
| NOT REQUIRED. BUT IF APPLICANT WANTS THEM TO BE PART OF |
| THE CONSTRUCTION DOCUMENTS, THEN REVISE THEM AS |
| FOLLOWS: |
| |
| A)SEPARATE ENERGY CALCULATIONS IS REQUIRED FOR EACH |
| BUILDING. MAIN HOUSE AND ACCESSORY STRUCTURE. SEC. |
| R101.3 FBC-ENERGY CONSERVATION. |
| |
| B)PROVIDE COMPLETE/CORRECT INFORMATION ON TOP OF FORM, |
| INCLUDING CORRECT OWNER'S NAME, BUILDER'S NAME. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C)PROVIDE CORRECT INFORMATION ON ITEM 1 ON PAGE 1. THIS |
| IS NOT NEW CONSTRUCTION. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| D)PROVIDE CORRECT A/C AREA. COORDINATE WITH ITEM #10(A) |
| ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E)PROVIDE CORRECT NUMBER OF BEDROOMS. COORDINATE WITH |
| ITEM #10(A) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| F)PROVIDE CORRECT UNDER ATTIC INFORMATION. ATTIC IS NOT |
| VENTED. COORDINATE WITH PLANS. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| G)PROVIDE CORRECT YEAR OF CONSTRUCTION ON PROJECT |
| INFORMATION ON PAGE 2. COORDINATE WITH ITEM #10(C) |
| ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| H)PROVIDE CORRECT BLOCKS, SPACES, FLOORS, CEILING, |
| WALLS, WINDOWS INFORMATION ON PAGE 2 AND 3. COORDINATE |
| WITH ITEM #10(A) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| I)PROVIDE CORRECT ROOF INFORMATION ON PAGE 2. REVISE |
| ROOF TYPE AND MATERIAL TO MATCH PLANS. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| J)PROVIDE CORRECT ATTIC INFORMATION ON PAGE 2. |
| COORDINATE WITH ITEM #10(F) ABOVE. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| K) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |