2022-03-25 09:41:14RESIDENTIAL (R3)ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120514
  
 NOTE:
 GARAGE CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1,
 SEC. 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW WORK SHALL COMPLY WITH THE MATERIALS
 AND METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
  
 1- THERE ARE TWO SEPARATE BUILDINGS IN THIS PROPERTY. A
 SEPARATE PERMIT APPLICATION AND SUB-PERMITS ARE
 REQUIRED FOR EACH BUILDING. PLEASE SUBMIT A SEPARATE
 PERMIT APPLICATION AND SUB-PERMITS FOR THE ACCESSORY
 STRUCTURE. SPECIFY VALUE FOR THE MAIN HOUSE AND VALUE
 FOR THE ACCESSORY STRUCTURE. SAME PLANS CAN BE USED.
 NOTE: SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 2- NEED TO PROVIDE SURVEY SHOWING ACCESSORY BUILDING
 SETBACKS. NEED TO VERIFY COMPLIANCE WITH THE FIRE
 RESISTANT CONSTRUCTION REQUIREMENTS OF SEC. R302.1 AND
 TABLE R302.1 FBC-RESIDENTIAL FOR NORTH AND WEST SIDE.
 NOTE: OPENING IN WALLS MAY NOT ALLOWED IF LESS THAN
 3'-0" SETBACKS.
  
 3- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE
 SPACE. TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR
 VAPOR BARRIER. ARCHITECT OF RECORD TO PROVIDE
 SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS
 REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R302.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW WOOD MULLIONS AS SPECIFIED ON PLANS. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS. SEC. R302.1
 FBC-RESIDENTIAL.
  
 6- REVISE WALL DISTANCE "A" SPECIFIED ON NOTES FOR
 COMPONENTS AND CLADDING. MINIMUM WALL DISTANCE IS 4'-0"
 NOT 3'-0". SEE FIGURE R302.2(7) FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
  
 7- DEFERRED SUBMITTALS:
 (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)ALL WINDOW TYPES SHOWN ON PLANS.
 B)ALL DOOR TYPES SHOWN ON PLANS.
 C)ROOF TILE AND FLAT ROOF SHOWN ON PLANS.
  
 8-ARCHITECT IS SPECIFYING R-30 FOAM INSULATION. PROVIDE
 ICC EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION
 TO VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 9- SUBMIT COMPLETE INFORMATION FOR THE PERIMETER
 CONCRETE WALL UNDER A SEPARATE PERMIT. SEC. 105.1 CITY
 AMENDMENTS.
  
 10- ENERGY CALCULATIONS SUBMITTED: THIS HOUSE IS A
 CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE
 NOT REQUIRED. BUT IF APPLICANT WANTS THEM TO BE PART OF
 THE CONSTRUCTION DOCUMENTS, THEN REVISE THEM AS
 FOLLOWS:
  
 A)SEPARATE ENERGY CALCULATIONS IS REQUIRED FOR EACH
 BUILDING. MAIN HOUSE AND ACCESSORY STRUCTURE. SEC.
 R101.3 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE/CORRECT INFORMATION ON TOP OF FORM,
 INCLUDING CORRECT OWNER'S NAME, BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE CORRECT INFORMATION ON ITEM 1 ON PAGE 1. THIS
 IS NOT NEW CONSTRUCTION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D)PROVIDE CORRECT A/C AREA. COORDINATE WITH ITEM #10(A)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)PROVIDE CORRECT NUMBER OF BEDROOMS. COORDINATE WITH
 ITEM #10(A) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F)PROVIDE CORRECT UNDER ATTIC INFORMATION. ATTIC IS NOT
 VENTED. COORDINATE WITH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 G)PROVIDE CORRECT YEAR OF CONSTRUCTION ON PROJECT
 INFORMATION ON PAGE 2. COORDINATE WITH ITEM #10(C)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)PROVIDE CORRECT BLOCKS, SPACES, FLOORS, CEILING,
 WALLS, WINDOWS INFORMATION ON PAGE 2 AND 3. COORDINATE
 WITH ITEM #10(A) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I)PROVIDE CORRECT ROOF INFORMATION ON PAGE 2. REVISE
 ROOF TYPE AND MATERIAL TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)PROVIDE CORRECT ATTIC INFORMATION ON PAGE 2.
 COORDINATE WITH ITEM #10(F) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 K) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  