Plan Review Notes
Plan Review Notes For Permit 21120473
Permit Number 21120473
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-12-10 12:12:33FIRE PROVISO NOTES: THE MANUAL ACTUATION SHALL BE
 BETWEEN 3 FT. AND 20 FT. OF THE APPLIANCES IN THE PATH
 OF EGRESS. A CLASS K PORTABLE FIRE EXTINGUISHER SHALL
 BE LOCATED WITHIN 30 FT. OF THE COOKING SURFACE WITH A
 PLACARD STATING THE HOOD SUPPRESSION SYSTEM IS TO BE
 USED PRIOR TO USING THE PORTABLE EXTINGUISHER.