2022-08-03 13:50:01 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN |
| DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH |
| FIRE RESCUE. |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THE LETTER FROM JEFFREY P. COLLINS, MS, PE HAS BEEN |
| RECEIVED AND ACCEPTED BY THE DIVISION OF FIRE |
| PREVENTION AS ACCEPTABLE IN ADDRESSING THE LIFE SAFETY |
| CONCERNS REGARDING CHANGE OF USE TO AN EDUCATIONAL |
| OCCUPANCY, SPECIFICALLY REGARDING THE FOLLOWING ITEMS: |
| |
| 5. PROVIDE FIRE DEPARTMENT ACCESS TO THE AREAS THAT ARE |
| BLOCKED OFF. THE WON DOORS CLOSING OFF THE STAIRWELLS |
| WILL NEED TO BE ACCESSIBLE FOR MEANS OF EGRESS FROM THE |
| STAIRWELL. KEYS FOR ENTRY MUST BE PROVIDED TO THE FIRE |
| DEPARTMENT. |
| 6. FIRE EXTINGUISHER PLACEMENT SHOWN ON REVISED LS2.0. |
| 8. A DOOR SCHEDULE WITH HARDWARE IS REQUIRED. EXISTING |
| DOORS PROVIDED IN SEPARATE DOCUMENT. |
| |
| TRAVEL DISTANCE COMPLIES WITH THE LIFE SAFETY CODE, |
| NFPA 101 (FFPC.) THE SPRINKLER SYSTEM FOR THE ENTIRE |
| BUILDING MUST BE FULLY OPERATIONAL. THE FIRE ALARM MUST |
| ALSO BE FULLY OPERATIONAL. |
| -SPRINKLER AND FIRE ALARM SYSTEMS REQUIRE SERVICE |
| TESTING BY APPROPRIATE LICENSED/CERTIFIED |
| CONTRACTOR(S). |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION PRIOR TO OCCUPANCY. |
| FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN |
| A FAILED FIRE INSPECTION. |
| |
| |
| PER CITY CODES, SITE IS SUBJECT TO FIELD INSPECTIONS, |
| REQUIRED TESTING AND APPROVAL PRIOR TO OCCUPANCY IN NEW |
| CLASSIFICATION. |
| |