2022-07-25 12:12:43 | THIS PLAN WAS REVIEWED AND FAILED BY LT. BRIAN DOLAN, |
| DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING |
| COMMENTS: |
| |
| - FIRE SPRINKLER PERMIT FROM 2013 IS NOT VALID FOR |
| CURRENT CHANGE OF USE REQUEST. |
| |
| - SPRINKLER SYSTEM REQUIRES EVALUATION FOR OPERABILITY |
| AND SUITABILITY FOR PROPOSED OCCUPANCY. |
| |
| - FIRE ALARM PERMIT FROM 2014 IS NOT VALID FOR CURRENT |
| CHANGE OF USE REQUEST. |
| |
| - FIRE ALARM SYSTEM REQUIRES EVALUATION AND TESTING FOR |
| OPERABILITY AND SUITABILITY FOR PROPOSED OCCUPANCY. |
| |
| - THE AREA SHOWN IN DRAWING DOES NOT ADDRESS AREA FOR |
| PROPOSED OCCUPANCY AREA IN CHANGE OF USE PERMIT REQUEST |
| |
| - ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE |
| ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND |
| SHOP DRAWINGS BY CERTIFIED CONTRACTORS. |
| |
| - INSTALLATION OF "LOCKED BARRIERS" FROM STAIRWELLS AS |
| PROPOSED REQUIRES REVIEW AND APPROVAL BY A FIRE |
| PROTECTION ENGINEER FOR SUITABILITY/POTENTIAL BARRIER |
| TO EGRESS OR INGRESS OF EMERGENCY PERSONNEL. |
| |
| PER EMAIL FROM FIRE MARSHAL CHIEF PETER LEDUC 15 JULY |
| 2022: |
| |
| |
| "SIR |
| |
| THANK YOU ONCE AGAIN FOR THE INFORMATION. |
| |
| YOU HAVE SUBMITTED INFORMATION FROM 2013-2015 AND I DO |
| NOT SEE ANY INDICATION THAT THIS INFORMATION HAS BEEN |
| REVIEWED/APPROVED BY A FPE MEETING THE CURRENT |
| REQUIREMENTS OF AN EDUCATIONAL OCCUPANCY. |
| |
| RESPECTFULLY SUBMITTED. |
| |
| |
| PETER LEDUC |
| DIVISION CHIEF/FIRE MARSHAL |
| WEST PALM BEACH FIRE DEPARTMENT" |
| |
| |