Plan Review Notes
Plan Review Notes For Permit 21120392
Permit Number 21120392
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2022-07-25 12:12:43THIS PLAN WAS REVIEWED AND FAILED BY LT. BRIAN DOLAN,
 DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING
 COMMENTS:
  
 - FIRE SPRINKLER PERMIT FROM 2013 IS NOT VALID FOR
 CURRENT CHANGE OF USE REQUEST.
  
 - SPRINKLER SYSTEM REQUIRES EVALUATION FOR OPERABILITY
 AND SUITABILITY FOR PROPOSED OCCUPANCY.
  
 - FIRE ALARM PERMIT FROM 2014 IS NOT VALID FOR CURRENT
 CHANGE OF USE REQUEST.
  
 - FIRE ALARM SYSTEM REQUIRES EVALUATION AND TESTING FOR
 OPERABILITY AND SUITABILITY FOR PROPOSED OCCUPANCY.
  
 - THE AREA SHOWN IN DRAWING DOES NOT ADDRESS AREA FOR
 PROPOSED OCCUPANCY AREA IN CHANGE OF USE PERMIT REQUEST
  
 - ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 - INSTALLATION OF "LOCKED BARRIERS" FROM STAIRWELLS AS
 PROPOSED REQUIRES REVIEW AND APPROVAL BY A FIRE
 PROTECTION ENGINEER FOR SUITABILITY/POTENTIAL BARRIER
 TO EGRESS OR INGRESS OF EMERGENCY PERSONNEL.
  
 PER EMAIL FROM FIRE MARSHAL CHIEF PETER LEDUC 15 JULY
 2022:
  
  
 "SIR
  
 THANK YOU ONCE AGAIN FOR THE INFORMATION.
  
 YOU HAVE SUBMITTED INFORMATION FROM 2013-2015 AND I DO
 NOT SEE ANY INDICATION THAT THIS INFORMATION HAS BEEN
 REVIEWED/APPROVED BY A FPE MEETING THE CURRENT
 REQUIREMENTS OF AN EDUCATIONAL OCCUPANCY.
  
 RESPECTFULLY SUBMITTED.
  
  
 PETER LEDUC
 DIVISION CHIEF/FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT"
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  