Plan Review Notes
Plan Review Notes For Permit 21120392
Permit Number 21120392
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-06-24 10:05:53PER NFPA 1, THE PLAN SET PRESENTED DOES NOT PRESENT
 SUFFIECIENT INFORMATION TO CONSIDER A LIFE SAFETY
 REVIEW REGARDING AN EDUCATIONAL FACILITY. PLEASE CITE
 NFPA 101 REQUIREMENTS AS SPECIFIED IN NFPA 101, CH. 14
 NEW EDUCATIONAL OCCUPANCIES.
  
 WHAT ARE THE PROPOSED CHANGES TO THE DESIGNATED AREAS
 ON THE PLAN SET?
  
 ARE CHANGES TO THE STAIRS PLANNED? ELEVATOR SHAFT?
  
 CHANGE OF OCCUPANCY TYPE TO EDUCATIONAL CAN NOT BE
 GRANTED UNTIL ALL REQUIREMENTS OF A NEW EDUCATIONAL
 OCCUPANCY AS DEFINED IN NFPA 101 CH. 14 ARE MET.
  