Date |
Text |
2022-07-12 16:39:28 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| FBC B 107.2.1, PROVIDE MORE DETAILED INFORMATION. |
| |
| CONSIDERING SECTIONS 1012.5.2 & 1012.6.2 OF THE FBC EB |
| THE EXISTING HEIGHT/AREA & WALL RATINGS HAVE BEEN MET. |
| HOWEVER, AS PER FBC EB 1012.4.2, THE MEANS OF EGRESS |
| DETAILS FROM FBC B CHAPTER 10 MUST BE IDENTIFIED. |
| |
| 1.) IDENTIFY THE PANIC HARDWARE ON EGRESS DOORS AS PER |
| SCTION FBC B 1010.1.10. |
| 2.) FBC B 107.2.1, INDICATE HOW THE ACCESS TO STAIRS AT |
| 1ST FLOOR WILL BE CLOSED OFF. |
| 3.) FBC B 107.2.1, PROVIDE A SIGNED LETTER FROM OWNER |
| AND DESIGNER OF RECORD AS TO HOW AND WHY THE TOTAL |
| OCCUPANT # IS AT 159 OCCUPANTS. CONSIDERING THE |
| EDUCATION OCCUPANCY AND FBC B TABLE 1004.5 WE NEED TO |
| BE SURE THAT WE WILL NOT HAVE AN OCCUPANCY ISSUE. FOR |
| EXAMPLE, A CONFLICT WITH THE FUTURE NUMBER OF OCCUPANTS |
| AND THE BATHROOM CAPACITY. |
| 4.) FBC B 468.3.5.2, INDICATE THE LOCATION OF STAFF |
| BATHROOMS AND SEPARATE STUDENT BATHROOMS. |
| 5.) FBC B 468.3.7, INDICATE HOW THE LIGHTING IS SET UP |
| TO MEET THE CODE REQUIREMENTS. AS THE EXISTING LIGHTING |
| FROM THE LATS OCCUPANCY (RESTAURANT) MAY NOT BE |
| SUFFICIENT. |
| |