2022-03-09 13:17:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT:21120392 |
| ADD: 2119 S DIXIE HWY. |
| CONT: BELACRIS CONSTRUCTION |
| TEL: 305-244-0277 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW / CHANGE OF OCCUPANCY |
| DATE: WED. MARCH 09TH/ 2022 |
| ACTION: DENIED |
| |
| |
| 1) THE VALUE OF $185.00 DOLLARS WAS GIVEN FOR A CHANGE |
| OF OCCUPANCY. THERE ARE SIGNED AND SEALED SHEETS FOR A |
| PREVIOUS PERMIT, THEY COULD ONLY BE USED FOR REFERENCE |
| ONLY. PLEASE PROVIDE A COMPLETE SET OF PLANS FOR A |
| CHANGE OF OCCUPANCY, EDUCATIONAL. |
| |
| 2) 2020 FBC-EXISTING BUILDING CODE SHOW COMPLIANCE FOR |
| ALL OF CHAPTER 10 FOR ALL TRADES, CHANGE OF OCCUPANCY, |
| 1001.2.1- 1013. |
| |
| 3) 2020 FBC-BUILDING 468 PRIVATE SCHOOLS SHOW |
| COMPLIANCE WITH 468.1- 468.3.7.5. |
| |
| 4) W 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY |
| THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING |
| MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; |
| SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR |
| TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; |
| FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL |
| EXTERIOR ELEVATIONS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 1. SITE REQUIREMENTS: |
| PARKING |
| FIRE ACCESS |
| VEHICLE LOADING |
| DRIVING/TURNING RADIUS |
| FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A |
| SPECIAL FLOOD HAZARD AREA |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE SECTION 503). |
| 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| INCLUDE THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE |
| RESISTANCE |
| 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| EARLY WARNING SMOKE EVACUATION SYSTEMS |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| RISER DIAGRAM |
| 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| INCLUDE THE FOLLOWING |
| REQUIREMENTS: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| EARLY WARNING |
| SMOKE CONTROL |
| STAIR PRESSURIZATION |
| SYSTEMS SCHEMATIC |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| SPECIFIC OCCUPANCY REQUIREMENTS |
| CONSTRUCTION REQUIREMENTS |
| HORIZONTAL EXITS/EXIT PASSAGEWAYS |
| |
| 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| SOIL CONDITIONS/ANALYSIS |
| TERMITE PROTECTION |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE/ COMPONENTS & CLADDING |
| STRUCTURAL CALCULATIONS (IF REQUIRED) |
| FOUNDATION |
| FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, |
| INCLUDING LOWEST FLOOR |
| ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT |
| MATERIALS |
| WALL SYSTEMS |
| FLOOR SYSTEMS |
| ROOF SYSTEMS |
| THRESHOLD INSPECTION PLAN |
| STAIR SYSTEMS |
| |
| 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM |
| INCLUDE THE FOLLOWING: |
| WOOD |
| STEEL |
| ALUMINUM |
| CONCRETE |
| PLASTIC |
| GLASS |
| MASONRY |
| GYPSUM BOARD AND PLASTER |
| INSULATING (MECHANICAL) |
| ROOFING |
| INSULATION |
| |
| 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| VERTICAL ACCESSIBILITY |
| TOILET AND BATHING FACILITIES |
| DRINKING FOUNTAINS |
| EQUIPMENT |
| SPECIAL OCCUPANCY REQUIREMENTS |
| |
| 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| LIGHT AND VENTILATION |
| SANITATION |
| 12. SPECIAL SYSTEMS: |
| ELEVATORS |
| ESCALATORS |
| LIFTS |
| 13. LOCATION AND INSTALLATION DETAILS. THE SPECIFIC |
| LOCATION AND INSTALLATION DETAILS OF EACH |
| FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER |
| SHALL BE SHOWN AND PROPERLY |
| IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER. |
| |
| 14) THE SURVEY SHOWS 2 BUILDINGS JUST WEST OF THE ALLEY |
| WAY, IS THERE ANY WORK TO BE COMPLETED UNDER THIS |
| PERMIT. |
| |
| 15) PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |