Plan Review Notes For Permit 21120381 |
Permit Number |
21120381 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-27 14:09:16 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE GENERATOR PAD DETAILS AND GENERATOR TO PAD | | ANCHORING FOR WINDLOADING. FBC-R301.1 | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | OPENINGS | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | |
|