Plan Review Notes For Permit 21120324 |
Permit Number |
21120324 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-10 13:03:50 | PLEASE SEE THE FIRE REVIEWERS COMMENTS BELOW: | | | | | | NFPA 96 | | | | 10.2.2* A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR | | EACH EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION | | SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE | | EXTINGUISHER. | | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION | | SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. | | AND 48 IN.)ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT | | OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY | | IDENTIFY THE HAZARD PROTECTED. INDICATE MOUNTING HEIGHT | | AND LOCATION. | | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE | | LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M | | (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) | | WITHIN A PATH OF EGRESS | | OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ. | | INDICATE LOCATION ON A FLOOR PLAN. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|